INSTALLATION INTRUCTIONS 

 

N.B. All installations should be carried out by a 
competent person and in line with current wiring 
regulations. 
 
WARNING 

 
The programmer should not be removed from back 
plate unless the unit is isolated from the electrical 
supply. 

 

 

1) Specification 

 

a)  Power Supply: 230 Vac ~ 50Hz 
b)  Rating: 3(1)A Total Load 
c) Mains 

Fuse: 

3A 

d)  Temperature control range : 0~35°C 
e)  Program Memory backup: 3Vdc Lithium CR 2032 
     (Memory sustains 30 days after outages) 
e)  Backlight (blue) Default : permanently ON 
f)  Protection Class: IP 20 
g)  Standard British Gas system wiring back-plate. 

 

 

2)  P or G Mode Selection 

 

 

a)  When “P” is selected each channel to be 

programmed independently. 

 
b)  When “G” is selected the CENTRAL HEATING 

channel controls the HOT WATER channel. 

 
 
 
 
 

 

 
 

3)  Day programming mode selection 

 

 
a)  The selection is made by switching the 3-way 

switch to the desired position, prior to installation. 

 
b) 

Reset the programmer after switching the 3-way 
switch to the desired position. A blunt, non 
metallic instrument should be used to press the 
reset button.

 

 
c)  24H: All 7 days of the week are programmed with 

the same programme times. 

 
d)  5/2D: All 5 week days can be programmed with 

the same programme times and the weekend 
days can be programmed with a different 
programme times. 

 
e)  7D: Each day of the week can be programmed 

with independent programme times.  

 

4)  Frost Protection function – selectable range 

5~20°C  

 
a) 

This Function is set to protect water pipes 
against freezing or to prevent the room from low 
temperature, when programmer is in 
programmed OFF or manual OFF. 

b) 

This function is activated by fitting one of the 

jumpers (provided) in the 

location, on the 

rear of the unit, prior to installation. 

 

c) 

Reset the programmer after fitting the above 
jumper. A blunt, non metallic instrument should 
be used to press the reset button. 

 

d) 

The 

 symbol will flash on the LCD to 

indicate that the FROST PROTECTION function 
is active. 

 

5)  Setting the Frost Protection set point 

 
a)  Move the selection switch to the “RUN” position 

 

b) 

Press both the 

 and the 

buttons 

to select the manual OFF position (i.e. “ON 3 2 1 
OFF”). 

 

c) 

Hold down both the “+” and “-” buttons at the 
same time for 5 seconds to enter the selection 
mode. 

 

d) 

Press either the “+” and “-” buttons to set the 
Frost Protection set point (between 5~20°C). 

 

e) 

Press the “OK” button to activate. 

SunPro2000 TWO–CHANNEL PROGRAMMER 
(with programmable room temperature and 
frost protection options) 