sunsei CC10000 Operating Instructions Download Page 2

Need help?

www.sunseisolar.com

+1 514.270.5770

Operating Instructions

Register your warranty

 online and enter to win an ICP Solar product. 

www.icpsolar.com/warranty

CHARGE

CONTROLLER

 CC10000

CAUTION: DO NOT EXCEED THE UNIT’S VOLTAGE AND 
CURRENT RATINGS

Do not 

exceed the maximum open circuit voltage (Voc) rating 

of 30V. This is the sum of the Voc of all solar panels in series.

Do not 

exceed the maximum current rating 10A. This is the 

sum of the peak operating current (Ip) of all the solar panels 
in parallel. 

Do not 

deviate from the recommended wiring instructions. 

INFORMATION

>

  The  charge  controller  SHOULD  NOT  BE  USED  in  direct 

sunlight or temperatures exceeding 122ºF (50ºC) or below 
-40ºF (-40ºC). It should be installed within 5 feet (1.5m) of 
the battery in a cool, dry and well ventilated area. Intended 
for indoor use.

>

  DO  NOT  USE  MORE  THAN  10A  (150W)  of  solar  power 

with the Sunsei™ CC10000.

>

  ALL  connections  should  be  in  PARALLEL  (Positive  to 

Positive,  Negative  to  Negative).  Ensure  that  connections 
are clean and solid. 

>

  Always CONNECT the BATTERY FIRST, and DISCONNECT 

the  BATTERY  LAST.  It  is  recomended  connecting  a  fuse 
close to the battery on wires extending from it, especially 
for longer runs. Follow electrical codes where applicable.

>

  For all additions or longer distances, use up to #6 (gauge) 

wires.  Always  CONNECT  the  BATTERY  FIRST,  and 
DISCONNECT the BATTERY LAST.

PROCEDURE

Mount charger on a dry non-flammable surface. Use mounting 
holes.

1.  CONTROLLER  TO  BATTERY  CONNECTION:  Connect 
positive  and  negative  wires  into  designated  positive  and 
negative  terminals  of  the  controller.  Then  carefully  connect 
wires to battery and/or fuse terminal (see wire selection table 
below).

2.  CONNECT  PANELS:  If  connecting  more  than  one  solar 
panel, connect the solar panels to the master cable in parallel, 
+ to + and - to -. 

3. CONTROLLER TO PANEL CONNECTION: Connect positive 
and  negative  master  cable  wires  to  designated  positive  and 
negative terminals of the charge controller. 

4. WIRE TYPE: When possible, use stranded wire instead of 
solid  wire.  Stranded  wire  does  not  fatigue  and  cause  loose 
connections over time as easily as solid wire. Use red wire for 
(+) and black for (-).

5. WIRE SIZE: Refer to the “WIRE GAUGE” charts below to 
determine the minimum size wire needed for each connection. 
Note that the bigger the wire, the lower the AWG. When using 
large stranded wire, you may need to divide the ends into two 
groups and straddle the screw on the terminal block.

RECOMMENDED WIRE GAUGE CHARTS

6. COMPLETE THE INSTALLATION OF PANELS, BATTERY 
AND LOAD

LOCATION

The  Sunsei

TM

  CC10000  should  be  mounted  where  it  can  be 

easily seen and reached as needed. Carefully consider how 
the wires are to be run from the solar panel to the controller 
and from the controller to the battery. The Sunsei

TM

 CC10000 

should  be  mounted  as  close  to  the  battery  as  possible  to 
reduce  voltage  drop  in  the  wires.  Wires  extending  from  the 
battery should be fused. Respect local electrical codes where 
applicable.

Cable Length (ft.)

0 to 5

5 to 10

10 to 15

15 to 20

SE-1200

14

14

14

14

SE-4000

14

14

14

12

SE-6000

14

14

12

10

SE-8000

14

12

10

8

Recommended Wire Gauge (AWG) Chart to limit voltage drop to 0.3V

Charge Controller to Battery

Recommended Wire Gauge (AWG) Chart to limit voltage drop to 0.5V

Panel to Charge Controller

Cable Length (ft.)

0 to 10

10 to 20

20 to 30

30 to 40

40 to 50

50 to 60

SE-1200

14

14

14

14

14

12

SE-4000

14

14

12

12

10

10

SE-6000

14

12

10

10

8

8

SE-8000

14

12

10

8

8

6