background image

ZigBee to DALI DT6 Controller

09.2411ZGDIM.04791

Function introduction

Important: 

Read All Instructions Prior to Installation

Input signal

Output

Power Supply

DALI Current Consumption

Operating temperature

Relative humidity

Dimensions(LxWxH)

Radio frequency

Product Data

• 

DO NOT install with power applied to device.

• 

DO NOT expose the device to moisture.

Safety & Warnings

ZigBee/Push

DALI signal

12-24VDC

<4mA

0-40°C

8% to 80%

45.5x45x20.3mm

2.4GHz

• 

ZigBee to DALI DT6 Controller based on ZigBee 3.0

• 

Receives ZigBee signal and outputs DALI signal to DALI line, 12-24VDC power supply

• 

Comply to DALI standard protocol IEC 62386-102, IEC 62386-207 and in compliance with DALI products from other 

international incorporations

• 

ZigBee end device that supports Touchlink commissioning

• 

Supports zigbee green power and can learn to max. 20 zigbee green power remotes

• 

Can directly pair to a compatible ZigBee remote through Touchlink

• 

Compatible with universal ZigBee gateway products

• 

Supports self-forming zigbee network without coordinator

• 

Enables to add devices to the self-formed zigbee network

• 

Compatible with universal ZigBee dim remotes

• 

DALI bus current consumption <4mA

• 

Enable to select Group control or Address control to DALI line by a rotary switch

• 

Enable to control 1 DALI Group of devices or 1 DALI Address on DALI line

• 

Enable to control all devices on DALI line via broadcast

• 

Enable to select any DALI Group (0-15) or DALI Address (00-63) to control by rotary switches

• 

Each DALI line can install multiple controllers for multi control points

• 

Waterproof grade: IP20

1. Select DALI Address/Group Control Mode:

1) A rotary switch is used to select Address/Group control mode.
2) When the rotary switch arrow is at Add. position, address control mode is selected.
3) When the rotary switch arrow is at Group position, group control mode is selected.

2. Select DALI Address to be Controlled:

1) When Address control mode is selected, use the two rotary switches for setting address number (00-64) to 
select the DALI address (00-63) you would like to control, the number equals to tens position plus units 
position.
2) Set the address number as 0, all DALI devices on the circuit will be controlled through broadcast.
3) Set the address number as X except 0 (01-64), control gear with DALI address X-1 will be controlled.
Note: if X is set as 64, control gears with DALI address 63 will be controlled by the controller.

3. Select DALI Group to be Controlled:

1) When Group control mode is selected, use the two rotary switches for setting group number to select the 

DALI group (0-15 selectable) you would like to control, the number equals to tens position plus units position.

2) This DALI controller enables on/off and dimming commands to be sent to 1 Group of devices on the DALI 

circuit. 

3) When group number is set as 0, all DALI devices on the circuit will be controlled through broadcast.

4) When group number is set as X except 0 (1-15), the controller will control DALI Group X-1.

Note: Please first group all DALI control gears on the circuit by a master controller.

Please refer to the detailed Group setting table as follows:

4. This ZigBee device is a wireless receiver that communicates with a variety of ZigBee compatible 

systems. This receiver receives and is controlled by wireless radio signals from the compatible ZigBee 

system.

Group Number 

Setting

DALI Group

Selected

0

Broadcast

1

0

2

1

3

2

4

3

5

4

6

5

7

6

8

7

9

8

10

9

11

10

12

11

13

12

14

13

15

14

Operation

Input Clusters

• 

0x0000: Basic

• 

0x0003: Identify

• 

0x0004: Groups

• 

0x0005: Scenes

• 

0x0006: On/off

• 

0x0008: Level Control

• 

0x0b05: Diagnostics

Output Clusters

• 

0x0019: OTA

ZigBee Clusters the device supports are as follows:

DA

DA

ZigBee to DALI Controller

Prog.

Rotary Switch to select 
Group or Address 
control to DALI circuit

DALI signal output

DC12-24V power input

Program key for factory
reset the controller

LED indicator

Add.

Group

1*(0~9) for setting
units position

10*(0~9) for setting
tens position

Rotary switches for setting DALI Group number (0-15) or 
Address number (0-63) to be controlled, the number equals to 
tens position plus units position

x1

x10

5

0

1

6

2

7

4

9

3

8

5

0

1

6

2

7

4

9

3

8

DC 12-24V

INPUT

V+

V-

DALI

OUTPUT

Reviews: