  Safety and Installation Instructions - Document 001-14158 Rev S 

 

 

© 2015 SunPower Corporation. All rights reserved. Specifications included in this manual are subject to change without notice. 

 Page | 2

 

Safety and Installation Instructions 

(United States and Canada) 

1.0

 

Introduction   

This manual provides safety and installation instructions for UL Listed 
SunPower photovoltaic (PV) modules that have the UL logo on the 
product label: 

 

    

 

 

1.1 Disclaimer of Liability 

The installation techniques, handling, and use of this product are beyond 
company control. Therefore, SunPower assumes no responsibility for loss, 
damage or expense resulting from improper installation, handling, or use.  

 

1.2 Underwriters Laboratories (UL) Listing Information 

This product meets or exceeds the requirements set forth by UL 1703 and 
ULC/ORD-C1703-01 for PV Modules. These Standards cover flat-plate PV modules 
and panels intended for installation on buildings or those intended to be 
freestanding. To satisfy the Listing for this product the modules must be mounted 
with a rack or standoff structure. The Listing does not include integration into a 
building surface because additional requirements may apply. This product is not 
intended for use where artificially concentrated sunlight is applied to the module. 

 

1.3 Limited Warranty 

Module limited warranties are described in full in the SunPower warranty 
certificates obtainable at 

www.sunpower.com

. In summary, the Limited 

Warranties do not apply to any of the following: 

Modules which in SunPower's absolute judgment have been subjected to misuse, 
abuse, neglect or accident; alteration; or improper installation, application or 
removal. This includes, but is not limited to, installation, application, or removal 
by any party other than a SunPower authorized dealer; non-observance of 
SunPower's installation, user’s and/or maintenance instructions; repair or 
modifications by someone other than an approved service technician of 
SunPower; power failure surges, lightning, flood, fire, accidental breakage, or 
other events beyond SunPower's control.  
 

 

2.0

 

Safety Precautions 

Before installing this product, read all safety instructions in this document. 

 

 

 

 

All installations must be performed in compliance with the National Electrical 
Code (NEC) and any applicable local codes. 

 

For Canadian jurisdictions, installations shall be in accordance with CSA C22.1, 
Safety Standard for Electrical Installations, Canadian Electrical Code, Part 1 

 

There are no user-serviceable parts within the module. Do not attempt to 
repair any part of the module.   

 

Installation should be performed only by qualified personnel.  

 

Do not stand on, drop, scratch, or allow objects to fall on modules as it may 
damage and void the warranty. 

 

Do not place anything on the modules, even for a moment because resulting 
residue may damage or stain the glass surface. 

 

If the front glass is broken, or the backsheet is torn, contact with any module 
surface or module frame can cause electric shock. 

 

Broken J-boxes or connectors are electrical hazards as well as laceration 
hazards. Installers should remove any such module from the array and 
contact SunPower for disposal instructions.   

 

Do not install or handle the modules when they are wet or during periods of 
high wind. 

 

SunPower recommends a conservative minimum cable bend radius of equal 
to or greater than

 

40 mm (1.5”).   

 

Contact SunPower if maintenance is necessary. 

 

Save these instructions!    

 

2.1 Fire Rating 

The module fire rating is Type 2 per UL1703, 2013 edition and Class C per 
UL1703, 2002 edition. Fire rating classification for any PV system using 
UL1703:2013 can only establish a fire rating in combination with the mounting 
system ratings normally found in the mounting system installation instructions. 

3.0

 

Electrical Characteristics 

 

Electrical characteristics of the modules are described in Table 1 below. Each 
module contains three bypass diodes.  For all modules, the maximum series fuse 
rating is 15A. 
 

Table 1: Electrical Characteristics

1

 

Module

Rated Power 

(W)

Voltage at 

Rated Power 

Vmpp (V)

Current at 

Rated Power, 

Impp (A)

Open Circuit 
Voltage  Voc 

(V)

Short Circuit 

Current, Isc (A)

Maximum 

System 

Voltage UL 

Vmax (V)

SPR-X22-360-COM

1000

SPR-X22-360

600

SPR-X21-345-COM

1000

SPR-X21-345

600

SPR-X21-335

SPR-X21-335-BLK

SPR-X20-327-COM

1000

SPR-X20-327

600

SPR-X20-327-BLK

600

SPR-X22-275

275

44.8

6.14

52.7

6.54

600

SPR-X21-255

255

42.8

5.95

51

6.3

600

SPR-X20-250-BLK 

250

42.8

5.84

50.9

6.2

600

SPR-X21-245

245

42.8

5.72

50.8

6.08

600

SPR-X19-310

SPR-X19-310-BLK

SPR-X19-240-BLK

240

42.8

5.61

50.6

5.98

600

SPR-E20-440-COM

440

72.9

6.04

86.5

6.5

1000

SPR-E20-435-COM

435

72.9

5.97

85.6

6.43

1000

SPR-E19-410-COM

410

72.9

5.62

85.3

6.01

1000

SPR-E20-327

600

SPR-E20-327-COM

1000

SPR-E19-320

320

54.7

5.86

64.7

6.24

600

SPR-E19-315

315

54.7

5.76

64.6

6.14

600

SPR-E19-310-COM

310

54.7

5.67

64.4

6.05

1000

SPR-E18-295-COM

295

54.2

5.45

63.3

5.83

1000

SPR-E20-245

245

40.5

6.05

48.8

6.43

600

SPR-E19-235

235

40.5

5.8

48.4

6.175

600

SPR-230NE-BLK

230

40.5

5.68

48.2

6.05

600

600

327

54.7

5.98

64.8

6.46

327

57.3

5.71

67.6

6.07

310

57.3

5.41

67.2

5.82

335

57.3

5.85

67.9

6.23

600

360

60.6

5.94

69.5

6.48

345

57.3

6.02

68.2

6.39

 
3.1 Bypass Diodes 

                                                 

1

 

For all models the Maximum System voltage for IEC standards is 1000V and 

maximum series fuse is 15A. For models not shown here, please contact SunPower 
technical support or visit 

www.sunpower.com

. Electrical parameters are measured at 

Standard Test Conditions (STC).

 

DANGER!

  Module interconnection cables pass direct current (dc) and 

are sources of voltage when the module is under load and when it is 
exposed to light. 

Direct current can arc across gaps and may cause 

injury or death if improper connection or disconnection is made; or 
if contact is made with module leads that are frayed or torn.

 Do not 

connect or disconnect modules when a current source is energizing 
the conductors. Modules may contain high voltage when 
interconnected with other modules.

 

IMPORTANT!

  Please read this manual in its entirety before 

installing, wiring, or using this product in any way. Failure to comply 
with these instructions will invalidate the SunPower Limited 
Warranty for PV Modules. 