Safety and Installation Instructions - Document 514744 Rev B 

 

 

©2015 SunPower Corporation. All rights reserved. Specifications included in this manual are subject to change without notice.

 

Safety and Installation Instructions 
(United States and Canada) 

IMPORTANT SAFETY INSTRUCTIONS 
SAVE THESE INSTRUCTIONS  
 

1.0

 

Introduction  

This manual provides safety and installation instructions for UL Listed 
SunPower AC photovoltaic (PV) modules carrying the UL logo on the 
product label (Fig. 1). 
 

 

  

Fig. 1 

 

 

 

1.1 Disclaimer of Liability 

The installation techniques, handling and use of this product are beyond company 
control. Therefore, SunPower does not assume responsibility for loss, damage, or 
expense resulting from improper installation, handling, or use. 

 

1.2 Nationally Recognized Testing Laboratory

 (NRTL) Listing Information 

This product meets or exceeds the requirements set forth by UL1703 and UL 1741 
for AC PV Modules. The UL 1703 Standard covers flat-plate PV modules and panels 
intended for installation on buildings or those intended to be freestanding. The UL 
1741  Standard  covers  inverters,  converters,  controllers,  and  interconnection 
system  equipment  for  use  with  distributed  energy  resources,  including  AC 
Modules.  The  NRTL  listing  does  not  include  integration  into  a  building  surface 
because additional requirements may apply. This product is not intended for use 
where artificially concentrated sunlight is applied to the module. 

 

1.3 Limited Warranty 

Module  limited  warranties  are  described  in  full  in  the  SunPower  warranty 
certificates  obtainable  at 

www.sunpower.com

.    In  summary,  the  Limited 

Warranties do not apply to any of the following: 

PV  modules  which  in  SunPower's  absolute  judgment  have  been  subjected  to: 
misuse, abuse, neglect, or accident; alteration, improper installation, application, 
or  removal.  Including,  but  not  limited  to  installation,  application,  or removal  by 
any  party  other  than  a  SunPower  authorized  Dealer;  non-observance  of 
SunPower's  installation,  user’s  and/or  maintenance  instructions;  repair  or 
modifications  by  someone  other  than  an  approved  service  technician  of 
SunPower; power failure surges, lightning, flood, fire, accidental breakage or other 
events outside SunPower's control. 

2.0

 

Safety Precautions 

Before installing this device, read all safety instructions in this document. 

 

 

 

 

Disconnect the utility AC source from all modules in the PV array before 
making or breaking electrical connections. 

 

It is imperative to use the supplied AC locking connectors in order to defend 
against untrained personnel disconnecting the modules after they have been 
installed. 

 

All installations must be performed in compliance with the National Electrical 
Code (NEC) and any applicable local codes.  

 

Installation should be performed only by authorized personnel.  

 

Remove all metallic jewelry prior to installing this product to reduce the 
chance of accidental exposure to live circuits. 

 

Use insulated tools to reduce your risk of electric shock. 

 

Do not stand on, drop, scratch, or allow objects to fall on modules. 

 

Broken glass, J-boxes, broken connectors, and/or damaged backsheets are 
electrical hazards as well as laceration hazards. An authorized person should 
remove the module from the array and contact the supplier for disposal 
instructions.   

 

Do not install or handle modules when they are wet or during periods of high 
wind. 

 

Contact your module supplier if maintenance is necessary. 

 

Save these instructions! 

3.0

 

Electrical Characteristics 

AC Output Characteristics: 
All AC module electrical output characteristics are listed in the Table 2 of the 
appendix. 
 
DC Internal Characteristics: 
All internal DC electrical characteristics of SunPower modules are listed in Table 2 
of the appendix.  
 
If an installation involves a SunPower AC module which does not appear on this 
list please consult the product label on the back of the module or visit 

www.sunpower.com

 for the product datasheet.  

 

3.1 Fire Rating 

The AC module maintains the same Type 2 fire rating associated with DC 
modules.  

4.0

 

Electrical Connections 

This unit or system is provided with fixed trip limits and shall not be aggregated 
above 30 kW on a single point of common connection.  
 
Modules  must  only  be  connected  using  supplied  AC  cabling  and  AC  cable 
accessories. Do not cut or alter any connectors or cables attached to modules. You 
must  use  the  proper  AC  transition  cable  adaptor  supplied  by  SunPower  when 
transitioning from the AC module cabling system to other wiring methods.  
The  connectors  on  SunPower  AC modules  ship  with  weatherproof  and  sunlight-
rated  AC  locking  connectors  which  after  connected  require  the  use  of  a  tool  to 
disconnect  module-to-module  connections.  This  defends  against  untrained 
personnel  disconnecting  the  modules  when  under  load  (see  Section  2.0).  AC 
connectors  are  rated  and  tested  to  interrupt  load  current;  however,  SunPower 
recommends that you always open the utility dedicated branch circuit protector to 
remove  power  before  plugging  or  unplugging  any  connectors;  but  a  local  AC 
disconnect is not required by SunPower.   
 
When installing AC modules the National Electric Code, ANSI/NFPA 70 wiring 
methods shall be used. 

 

4.1 Equipment Grounding

 

In accordance with the NRTL Listing of this product and to reduce the possibility of 
electrical  shock,  all  metallic  components  of  AC  modules  shall  be  grounded. 
SunPower  AC  modules  shall  be  grounded  using  the  integrated  equipment 
grounding conductor contained within the factory-installed AC module cables and 
the supplied AC transition cable. This grounding conductor must be connected to 
the  building  or  structure’s  equipment  grounding  system  and  AC  grounding 
electrode system using NEC-compliant methods. All metallic components of the AC 
module  are  bonded  together  in  the  factory  so  that  no  additional  grounding 
conductor  attachment  to  the  AC  module  is  required.  This  method  meets  NEC 
requirements for grounding. 

Important!

  Please read this instruction manual in its entirety before 

installing, wiring, or using this product in any way. Failure to comply 
with these instructions will invalidate the SunPower Limited 
Warranty for PV Modules. 

Danger!

  AC Modules generate internal direct current (DC) and output 

alternating current (AC) and are sources of voltage when the module is 
under load and when it is exposed to light. 

Electrical currents can arc across 

gaps and may cause injury or death if improper connection or 
disconnection is made, or if contact is made with module leads that are 
frayed or torn.

  

Summary of Contents for Equinox SPR-E19-320-C-AC

Page 1: ... for AC Modules United States and Canada Contents of this manual are subject to change without notice For the latest guide please refer to www sunpower com PVInstallGuideACModule SunPower Corporation www sunpower com Document 514744 Rev B ...

Page 2: ...ceration hazards An authorized person should remove the module from the array and contact the supplier for disposal instructions Do not install or handle modules when they are wet or during periods of high wind Contact your module supplier if maintenance is necessary Save these instructions 3 0 Electrical Characteristics AC Output Characteristics All AC module electrical output characteristics are...

Page 3: ... resulting load rating achieved for each module configuration Fig 2 Mounting locations for SunPower modules Table 1 Mounting Configurations and Load Resistance Module Configuration Mounting configuration valid mounting location in mm Load rating Wind up down Snow down Module size Frame type frame color End mount A1 Pressure clamp or clip B1 Frame holes C1 96 cell G5 black 300 400 3000Pa 6000Pa 50 ...

Page 4: ...of modules is recommended but is not required Periodic cleaning has resulted in improved performance levels especially in regions with low levels of annual precipitation less than 18 25 inches 46 3 cm Consult your dealer or supplier about recommended cleaning schedules for your area To clean a module wash with potable non heated water Normal water pressure is more than adequate but pressurized wat...

Page 5: ...PORATION Safety and Installation Instructions Document 514744 Rev B 2015 SunPower Corporation All rights reserved Specifications included in this manual are subject to change without notice Fig 3 96 Cell AC Modules ...

Reviews: