All-in-one solar charge inverter 26
Parameter
no.
Parameter
name
Settings
Description
16
Battery
equalization
enable
[16] DIS
Equalizing charge is disabled
[16] ENA
default
Equalizing charge is enabled, only valid for
vented lead-acid battery and sealed lead-acid
battery
17
Battery
equalization
voltage
[17] 29.2V
default
Equalizing charge voltage; setting range:
24V~29.2V, with a step of 0.2V; valid for vented
lead-acid battery and sealed lead-acid battery
18
Battery
equalized
time
[18] 120
default
Equalizing charge time; setting range:
5min~900min, with a step of 5 minutes; valid
for vented lead-acid battery and sealed lead-
acid battery
19
Battery
equalized
time out
[19] 120
default
Equalizing charge delay; setting range:
5min~900min, with a step of 5 minutes; valid
for vented lead-acid battery and sealed lead-
acid battery
20
Battery
equalization
interval
[20] 30
default
Equalizing charge derating time, 0~30days,
with a step of 1 day; valid for vented lead-acid
battery and sealed lead-acid battery
21
Battery
equalization
immediately
[21] DIS
Stop equalizing charge immediately.
[21] ENA
default
Start equalizing charge immediately.
22
Power saving
mode
[22] DIS
default
Power saving mode disabled.
[22] ENA
After the power saving mode is enabled, if the
load is null or less than 50W, the inverter
output is turned off after a delay for a certain
period of time. When the load is more than
50W, the inverter automatic restart.
23
Restart when
over load
[23] DIS
Automatic restart when overload is disabled. If
an overload occurs and the output is turned off,
the machine will not restart.
[23] ENA
default
Automatic restart when overload is enabled. If
an overload occurs and the output is turned off,
the machine will restart after a delay of 3
minutes. After it reaches 5 cumulative times,