Suniva OPTIMUS OPT240-60-4-1 Series Installation And Instruction Manual Download Page 3

OPT2XX-60-4-1YY IEC & UL EN 

 

SI&IM _2 Rev 4 

Page 3 

 

 

Figure 5: SolKlip Grounding Diagram 

Wiring 

  Connect modules using the supplied Tyco type connectors in 

series  or  parallel 

configurations  according  to  the  “+”  male 

neutral  (part  6-1394461-

2)  or  “-”  female  negative  (part 

1394462-4). 

  Only  same  type  of  Tyco  connector  shall  be  used  in 

connections  to  ensure  the  reliability  of  the  electrical 
connection. 

  For  conductor  utilize  suitable 

“Wet  or  Dry”  type  sunlight 

resistant  cable  (PV-Wire,  or  USE-2  type)  with  temperature 
rating  of  90 

C  or  higher  and  sized  12  AWG  or  larger.  

Paralleled  configurations  may  require  greater  wire  size  to 
accommodate  increase  current.  Ensuring  proper  conductor 
sizing is the responsibility of the installer. 

Junction Box 

  Do not open the junction box or change inter-module wiring. 

All  wiring  connections are made in the  factory and  doing  so 
may void the warranty.   

Bypass Diodes 

  3  Schottky  type  bypass  diodes  are  pre-assembled  in  each 

module.  

  Do not uninstall these diodes. 

  Bypass Diode Ratings: V

RRM

: 40 V, I

FAV

: 16 A @75 

Series/Parallel Configurations 

  Series  or  Parallel  configurations  must  be  restricted  to  a 

maximum  system  voltage  of  600  VDC  (UL)  or  1000  VDC 
(IEC).  

  Voltage  and  current  are  temperature  dependent  and 

systems  should  be  designed  to  allow  for  variations  due  to 
local conditions.   

  The voltage of modules in series connections will be equal to 

the sum of the individual voltages.   

  The current of modules in parallel  connections will be equal 

to the sum of the individual currents. 

  Refer  to  the  electrical  characteristics  for  the  values  of  Isc 

and Voc. 

Series and Parallel interconnection restrictions  

  At  standard  conditions  (AM1.5G,  25 

C)  the  number  of 

allowable modules in series is equal to the maximum system 
voltage  divided  by  the  Open  Circuit  voltage.  The  number  of 
modules  in  series  should  be  constrained  by  the  expected 
minimum  ambient  temperature,  module  V

oc

  temperature 

coefficient (β), and module V

oc

.  

  Suniva  recommends  a  maximum  of  21  modules  connected 

in series to allow for a minimum ambient temperature - 40 C 
to prevent an open circuit voltage in excess of 1000 V. 

  Suniva  recommends  a  maximum  of  12  modules  connected 

in  series  to  allow  for  an  ambient  temperature  -  40  C  to 
prevent an open circuit voltage in excess of 600 V.  

  At  standard  conditions  (AM1.5G,  25 

C)  modules  in  parallel 

without fuse protection are not allowed. 

  Suniva  recommends  that  no  modules  be  connected  in 

parallel  without  over  current  protection.  2  or  more  modules 
may be connected in parallel with over current protection. 

Over Current Protection 

  Series or parallel connections of modules or strings must be 

provided  adequate  over  current  protection  such  as  a 
recognized  circuit  breaker  or  fuse  meeting  minimum 

requirements listed in the Product Information section of this 
manual  and  be  certified  and  properly  rated.  System  design 
and  protection  for  any  series/parallel  configuration  must  be 
verified by a certified engineer and is the responsibility of the 
system  integrator  as  currents  may  exceed  1.25  times  I

SC

 

under some conditions.

 

Disconnection Under Load 

  Do NOT disconnect or connect module under load. 

  Modules  will  produce  electricity  even  under  low  light 

conditions.    Treat  modules  as  if  they  are  live  electrical 
equipment.  

  To avoid electric shock and injury, completely cover the front 

of  the  module  with  an  opaque  material  and  disconnect  the 
module  from  all  electrical  connections  before  disconnecting 
or connecting module wiring. 

 

Maintenance 

Maintenance is recommended to ensure optimal performance: 

  Depending on local conditions, periodically inspect and clean 

the  surface  of  the  module  with  water  and  a  soft  cloth  or 
sponge  when  the  modules  surface  becomes  dirty  and  rain 
water is insufficient to remove dirt/debris. 

  Never clean the modules during the middles of the day when 

the glass is hot to avoid injury. 

  Never  scratch  or  rub  away  any  dirt  when  the  modules  are 

dry. 

  Check the electrical and mechanical connections annually to 

ensure  all  the  connections  are  secure,  tight,  clean  and  free 
of corrosion. 

Disclaimer of Liability 

Suniva does not assume responsibility and expressly disclaims 
liability  for  loss,  damage  or  expense  arising  out  in  any  way 
connected  with  installation,  operation,  use  or  maintenance  by 
using  this  manual.  Suniva  assumes  no  responsibility  for  any 
infringement of patents or other rights of third parties that may 
result  from  use  of  the  module.  No  license  is  granted  by 
implication  or  otherwise  under  any  patent  or  patent  rights. 
Suniva  reserves  the  right  to  make  changes  to  the  product, 
specifications or this manual without prior notice. 

Electrical Characteristics 

For OPTXXX-60 Series modules ending in 100 

Module ID 

P

MP 

[W]  V

OC

 [V]  I

SC

 [A]  V

MP

 [V]  I

MP

 [A] 

OPT240-60-4-1YY 

240 

37.2 

8.84 

28.9 

8.30 

OPT245-60-4-1YY 

245 

37.5 

8.89 

29.4 

8.35 

OPT250-60-4-1YY 

250 

37.7 

8.98 

29.6 

8.44 

OPT255-60-4-1YY 

255 

37.9 

9.05 

30.0 

8.50 

OPT260-60-4-1YY 

260 

38.1 

9.08 

30.2 

8.60 

OPT265-60-4-1YY 

265 

38.3 

9.12 

30.7 

8.64 

 
For OPTXXX-60 Series modules ending in 101, 1B0 or 1B1 

Module ID 

P

MP 

[W]  V

OC

 [V]  I

SC

 [A]  V

MP

 [V]  I

MP

 [A] 

OPT235-60-4-1YY 

235 

37.1 

8.73 

28.7 

8.18 

OPT240-60-4-1YY 

240 

37.3 

8.76 

29.2 

8.23 

OPT245-60-4-1YY 

245 

37.6 

8.84 

29.5 

8.30 

OPT250-60-4-1YY 

250 

37.8 

8.90 

30.0 

8.34 

OPT255-60-4-1YY 

255 

38.1 

8.96 

30.2 

8.45 

OPT260-60-4-1YY 

260 

38.3 

9.01 

30.5 

8.52 

OPT265-60-4-1YY 

265 

38.3 

9.12 

30.7 

8.64 

 