Quick User Manual
2 Electrical Connection
15
2.9
DRED Connection
The inverter supports the DRM (Demand Response Mode) function as specified in
AS/NZS 4777:2015. The terminal block inside the inverter is used for connecting to a
demand response enabling device (DRED). The DRED asserts DRMs. The inverter
detects and initiates a response to all supported demand response commands
within 2s. The following table lists the DRMs supported by the inverter.
Tab. 2-1
DRMs Supported by the Inverter
Mode
Explanation
DRM0
The inverter is in the state of “Key-stop”.
DRM1
The import power from the grid is 0.
DRM2
The import power from the grid is no more than 50 % of the rated power.
DRM3
The import power from the grid is no more than 75 % of the rated power.
DRM4
The import power from the grid is 100 % of the rated power, but subject to
the constraints from other active DRMs.
DRM5
The export power to the grid is 0.
DRM6
The export power to the grid is no more than 50 % of the rated power.
DRM7
The export power to the grid is no more than 75 % of the rated power.
DRM8
The export power to the grid is 100 % of the rated power, but subject to the
constraints from other active DRMs.
The DRED may assert more than one DRM at a time. The following shows the priority
order in response to multiple DRMs.
Multiple Modes
Priority Order
DRM1…DRM4
DRM1 > DRM2 > DRM3 > DRM4
DRM5…DRM8
DRM5 > DRM6 > DRM7 > DRM8
Summary of Contents for SH5K
Page 1: ...SH5K QUEN Ver14 201708 Version 1 4 Quick User Manual SH5K Grid Connected Hybrid Inverter ...
Page 2: ......
Page 4: ...II System Overview ...
Page 5: ...III ...
Page 6: ...IV ...
Page 7: ...V ...
Page 8: ...VI ...
Page 9: ...VII ...
Page 10: ...VIII ...
Page 32: ...3 Commissioning Quick User Manual 20 Fig 3 2 Initial Settings ...