31
6.4
Backup Wiring Diagram
F
Fo
orr A
AU
U//N
NZ
Z
For Australia and New Zealand, the neutral cable of GRID side and BACK-UP side must
be connected together. Otherwise BACK-UP function will not work.
N
NO
O..
S
SH
H3
3..0
0//3
3..6
6//4
4..0
0//5
5..0
0//6
6..0
0R
RS
S
①
40A/600V DC breaker *
②
≤63A/230V/400V AC breaker
③
32A/230V/400V AC breaker
④
Depends on loads
⑤
Depends on household loads and inverter capacity
⑥⑦
30mA RCD (Comply with local regulation)
Note 1: * If the battery is integrated with a readily accessible internal DC breaker, no ad-
ditional DC breaker is required.
Note 2: The values in the table are recommended values and can be set to other values
according to actual conditions.
Note 3: The rated current of breaker ② is suggested to lower than that of breaker ⑤.
Note 4: If the rated current of on-site power cables are lower than those recommended
above, the breakers specification should be considered to match the power cables in
first priority.
Note 5: The AC port takes power from the grid and is set according to the grid circuit
breaker.
F
Fo
orr o
otth
he
err c
co
ou
un
nttiirre
ess
For other countires, the following diagram is an example for grid systems without special
requirement on wiring connection.
User Manual