Parameters of LCD
7.1
Communication Parameters
Improper communication parameter configuration may lead to inverter
communication failure!
Follow strictly the instructions of the plant staff to configure the communication
parameters.
There are the standard RS485 communication and Network communication. User can set the
communication address and protocol through the LCD screen when the hardware connection is
complete and the inverter is energized.
Proceed as follows to set the communication parameters:
Step 1
Tap “Function” from the default menu;
Step 2
Tap “Set-parameter”;
Step 3
Tap “Com-parameter” after entering the correct password.
Set parameter from the Serial Port Parameter interface for RS485 serial communication;
Set parameter from the Network Parameter interface for Network communication
7.1.1
Serial Port Parameter Setting
Click “Serial port param” to enter the following interface.
Three parameters pertinent to RS485 serial port communication can be set according to the
parameter range shown on the display.
“Address” is prescribed by the plant staff and the address for each inverter must be unique when
there is more than one inverter. “Baud” and “protocol” are selected according to the
communication method adopted.
Enter the device address with the aid of the pop-up keypad while select the Baud rate and
communication protocol through the pull-down list.