10 Operation of LCD Display
User Manual
78
10.10
Running Parameters Setting
10.10.1 Main Menu of Run-param
Main Screen(Press
ENTER
)
→
Menu screen(Press
j
×
3)
→
Set-param(Press
ENTER
)
→
Enter password(Press
ENTER
, Press
j
)
→
Run-param(Press
ENTER
)
On the “Run-param” screen, Press
j
to move arrow to
one item and Press
ENTER
to start this item setting.
For each item setting,
Press
h
to move cursor right and
Press
j
to set the appropriate value.
Confirm by Pressing
ENTER
.
Tab. 10-4
Specification of Running Parameters
Parameter
Explanation
Default
Range
Standby
time
The time from inverter initialization to
inverter feeding power to grid.
20s 20…255s
Recover
time
The time from the fault is cleared to
inverter feeding power to grid.
30s
[IT: 300s]
0…900s
P-W limits
Inverter active power limits.
100.0%
0...100%
Q-Var
switch
Whether to start inverter reactive
power adjustment function.
[Pf]
[Pf] / [Qt] / [Off]
/ [Q(P)] / [Q(U)]
PF Power
factor
+1.000
-1.000…-0.800 /
+0.800…+1.000
Q-Var limits
Inverter reactive power limits
0.0%
0...+100% /
0…-100%