72
P
Pa
arra
am
me
ette
err
D
De
effiin
niittiio
on
n//S
Se
ettttiin
ng
g
d
de
essc
crriip
pttiio
on
n
R
Ra
an
ng
ge
e
QP_P1
—
10.0%~100.0%
QP_P2
—
20.0%~100.0%
QP_P3
—
20.0%~100.0%
QP_K1
—
Curve A/Curve
C:0.800~1.000
Curve B: [-0.600~0.600]*-
Active Overload Rate/1000
QP_K2
—
Curve A/Curve C:
0.800~1.000
Curve B: [-0.600~0.600]*-
Active Overload Rate/1000
QP_K3
—
Curve A/Curve C:
0.800~1.000
Curve B: [-0.600~0.600]*-
Active Overload Rate/1000
QP_EnterVoltage
—
100.0%~110.0%
QP_ExitVoltage
—
90.0%~100.0%
QP_EXitPower
—
1.0%-20.0%
QP_EnableMode
—
Yes/No
Q(U)Curve
Selection of Q(U) curve.
Curve A/Curve B/Curve C*
QU_V1
Pre-set grid voltage U1 that
is reactive according to the
grid voltage
80.0%~100.0%
QU_Q1
Pre-set proportion of reactive
power according to the grid
voltage U1
[-60.0%-0]* Overload
Rate/1000
QU_V2
Pre-set grid voltage U2 that
is reactive according to the
grid voltage.
80.0%~100.0%
QU_Q2
Pre-set proportion of reactive
power according to the grid
voltage U2.
[-60.0%-60.0%]* Overload
Rate/1000