User Manual
10 Operating the LCD Menu
91
Parameter
Explanation
Default
Range
Feed Setting
Enable/disable
the
function of limiting
the feed power.
For Australia: ON
For others: OFF
ON/OFF
Feed
Power The upper limit
value of feed power.
For Australia: 092.0%
For others: 100.0%
0...100%
10.11.2 Reactive Power Regulation
The inverter provides reactive power regulation function. Use the “
Q-Var switch
”
parameter to activate this function and select proper regulation mode.
Regulation Mode
Explanation
Pf
The reactive power can be regulated by the parameter
PF
(Power Factor)
.
Qt
The reactive power can be regulated by the parameter
Q-Var
limits
(in %).
Off
The
PF
is limited to +1.000, and the “
Q-Var limits”
is limited to
0.0%.
Q(P)
The PF changes with the output power of the inverter.
Q(U)
The reactive power ratio changes with the grid voltage.
“
Pf
” Mode
The reactive power can be regulated by the parameter
PF
on the Run-param screen.
“
Qt
” Mode
The reactive power can be regulated by the parameter
Q-Var limits (in %)
on the
Run-param screen.
“
Off
” Mode
The
PF
is limited to +1.000, and the
Q-Var limit
is limited to 0.0%.
“
Q(P)
” Mode(when the country selection is not “IT”)
The PF changes with the inverter output power.
If the country selection is not “IT” (Italy), after
selecting Q(P) Mode,
Press
ENTER
to enter the
“Run-param” submenu.
For each item setting,
Press
to move cursor right
and
Press
to set the appropriate value. Confirm
settings by Press
ENTER
.