User Manual
18
Step 2
Pass the cable with the wire designation "DC+" through the waterproof
terminal "INPUT DC+", and reserve an appropriate length margin.
Step 3
Strip the protective layer and insulation layer of the cable to expose the
copper core of the wire L≈25mm, crimp the cable to an appropriate DT
terminal, and insert it into a heat shrink tube.
L=D+5
D
3
2
1
2
1
Step 4
Fix the crimped DT terminal to the input terminal.
For copper wire, the fixing method is as shown in the figure below, and the
tightening torque is 34~40N.m.
A
C
D
E
D
E
F
B
Figure 5-1
Copper wire connection diagram
A
B
C
D
E
F
Copper
bar
Copper
connecting
terminal
M10 bolt
Spring
cushion
Flat
washer
Nut
For aluminum wire, the fixing method is as shown in the figure below, and the
tightening torque is 34~40N.m.