background image

The performance of solar water heating systems in the 
Northern Hemisphere is optimized when the collector is 
mounted  facing  True  South.  Performance,  however, 
suffers  very  little  when  the  collector  is  oriented  no 
more than 45

°

 East or West of True South. The collec-

tor  should  not  be  shaded  by  any  permanent  obstacle 
between  9:00  a.m.  and  3:00  p.m.  on  any  day  of  the 
year. 

4.2 Collector Tilt 

Optimal annual efficiency is achieved by tilting the so-
lar collector at and angle that equals your latitude plus 
an additional 10

°

. This tilt angle favors the lower winter 

sun when the collector performance is at its lowest and 
minimizes  overheating  during  the  hottest  summer 
months. 

To  ensure  proper  water  drainage  from  the  glazing  the 
collector must be sloped from horizontal. Never mount 
the  collector  parallel  to  a  flat  roof.  Use  SunEarth 
RexRack, Landscape Rack or Universal Tilt Kit products 
to  raise  the  collector  to  a  proper  angle.  The  minimum 
acceptable tilt angle from horizontal is 15

°. 

 

 

The solar collectors in a two collector staggered mount 
installation must be spaced far enough apart to prevent 
winter  shading  when  the  sun  is  at  its  lowest  angle  on 
the winter solstice. 

4.3 Basic Mounting Procedures 

The  SunEarth  solar  collector  in  your  Cascade  2  Drain-
back solar system must be mounted in a vertical orien-
tation  parallel  to  the  slope  of  the  roof.    See  Figure  1.  
This orientation allows the internal riser tubes to rapid-
ly drain when the circulation pump shuts off.  

CRITICAL:  Both  the  collectors  and  the  solar  loop 
piping  must  be  sloped  to  drain  away  from  the 

highest point in the system back to the drainback 
reservoir.  

The  minimum  required  slope  is  1/4”  vertical  drop  per 
foot of horizontal piping run (2% minimum slope).  Use 
the steepest slope possible on the return line piping to 
the drainback reservoir. Water will drain down both the 
return tubes directly to the drainback reservoir and the 
supply tubes by spinning the pump impeller in the re-
verse direction. 

The  collector  should  be  mounted  as  close  to  the  stor-
age tank as possible to minimize heat loss in the piping 
runs. If the home has attic access, mounting the collec-
tors  near  the  roof  peak  provides  for  additional  attic 
workspace. 

The  solar  collector  should  be  mounted  on  the  roof  in 
accordance with these general principles: 

4.3.1  The  most  important  structural  considerations  is 
to securely anchor the solar collector and the SunEarth 
mounting  hardware  to  the  structural  members  of  the 
roof with stainless steel hanger bolts, lag bolts, stand-
off  mounts  or  other  approved  roof  attachment  meth-
ods. The solar collector shall be attached to the mount-
ing  hardware  as  detailed  in  Figures  (6-9).  (Note:  The 
drawings  in  the  manual  detail  mounting  hardware  for 
the  SunEarth  Empire,  Imperial,  SunBelt  and  Ther-

moRay series collectors.) 

4.3.2  The collector should be raised from the roof sur-
face to allow for rainwater and debris to pass under the 
collectors and for proper ventilation of the roofing ma-
terial.  There  should  be  at  least  1

1

/

2

”  of  clearance  be-

tween the roof surface and the bottom of the solar col-
lectors. Local codes may require greater clearance and 
shall be followed accordingly. 

4.3.3  When  selecting  mounting  hardware  and  fasten-
ers  it  is  extremely  important  to  avoid  galvanic  corro-
sion  resulting  from  the  direct  contact  of  incompatible 

STRUT ON FOOT MOUNT FOR 

COMPOSITION ROOF 

Fig.6 

COLLECTOR 

C-SSN 

FOOT MOUNT 

FLASHING 

STAINLESS LAG BOLT 

REXRACK 

Fig.5 

FRONT   
MOUNTING FOOT 

REAR 
TELESCOPING LEG 

SUPPORT STRUT 

C-SSN 

Summary of Contents for CASCADE 2

Page 1: ...SRCC OG SRCC OG 300 Certified Solar Water Heating System 300 Certified Solar Water Heating System Installation Operation and Maintenance Manual Installation Operation and Maintenance Manual ...

Page 2: ...stem certification is granted to SunEarth by the SRCC It may not be used for any commercial purpose without prior written consent of SunEarth SunEarth must approve any deviation from the mate rials and methods described in this manual in writing The Cascade 2 Drainback solar water heating systems can be protected against freeze damage to temperatures as low as 50ºF 46ºC This system should not be i...

Page 3: ... Isolation Procedures 14 8 Vacation procedures 14 9 Maintenance and Troubleshooting 14 10 Cascade 2 System Component Parts 15 11 Estimated Component Life 16 12 System Operating Parameters 16 Appendix A Approved Primary Components 18 Appendix C System and Component Labels 22 Appendix F SunEarth Collector Warranty Statement 24 Appendix G SRCC OG 300 Certified System Model Numbers 26 Appendix H Suppl...

Page 4: ...ng to prevent con tact with HOT water NOTICE Mixing valves should be installed to reduce the point of use water temperature by mixing hot and col wa ter in branch water lines Contact a licensed installer or the local plumbing authority for further information The temperature of the water in the water heater can be regulat ed by setting the temperature dial of the adjustable surface mounted thermos...

Page 5: ...cian or the local utility SAFETY PRECAUTIONS Have the installer show you the location of the circuit breaker and how to shut it off if necessary Turn off the circuit breaker if the water heater has been subjected to over heating fire flood or physical damage or if the ECO fails to shut off Read this manual entirely before in stalling or operating the water heating system Use this appliance only fo...

Page 6: ...e fluid water in the collector array and solar loop piping drains back by gravity into the drainback storage reservoir when the pump stops circulating Air replaces water in the col lector array and solar loop piping to prevent it from freezing when the pump is off This manual is intended as a basic solar water heating primer Our goal is to familiarize you with the proper installation operation and...

Page 7: ...r of any existing roof damage or necessary repairs 3 5 Structural Considerations The collectors must be located in a structurally sounds area of the roof Penetrations into structural members must not compromise the structural properties of the member ENSURE THAT ALL STRUCTURAL MEMBER PENE TRATIONS COMPLY WITH APPLICABLE CODES The collector mounting method must be capable of maintaining the require...

Page 8: ...nEarth Solar Collector s 2 3 4 Temperature Sensor 5 6 7 8 22 Ball Valve 11 24 35 36 Combination Valve 9 Pressure Relief Valve 10 Drain Back Tank 12 13 Pump 14 Heat Exchanger 17 Differential Temperature Controller 18 Heating Element Tank Thermostat 19 20 Temperature and Pressure Relief Valve 21 Mixing Valve 23 Water Heater 25 Solar Tank 22 35 ROOF JACKS 36 ...

Page 9: ...l Valve 11 24 35 36 Combina tion Valve 9 Pressure Relief Valve 10 Drain Back Tank 12 13 Pump 14 Heat Exchanger 17 Differential Temper ature Controller 18 Heating Element Tank Thermostat 19 20 Temperature and Pressure Relief Valve 21 Mixing Valve 23 Water Heater 25 Solar Tank 20 48 min T1 21 9 17 4 3 10 11 12 13 14 T3 PIPE INSULATION T2 22 24 23 25 35 ROOF JACKS 36 ...

Page 10: ...25 1 SunEarth Solar Col lector s 2 3 4 Temperature Sensor 5 6 7 8 22 Ball Valve 11 24 35 36 Combina tion Valve 9 Pressure Relief Valve 10 Drain Back Tank 12 13 Pump 14 Heat Exchanger 17 Differential Temper ature Controller 18 Heating Element Tank Thermostat 19 20 Temperature and Pressure Relief Valve 21 Mixing Valve 23 Water Heater 25 Solar Tank 35 ROOF JACKS 36 ...

Page 11: ...slope is 1 4 vertical drop per foot of horizontal piping run 2 minimum slope Use the steepest slope possible on the return line piping to the drainback reservoir Water will drain down both the return tubes directly to the drainback reservoir and the supply tubes by spinning the pump impeller in the re verse direction The collector should be mounted as close to the stor age tank as possible to mini...

Page 12: ...tions The PEX tubing shall not be exposed to sunlight Water must be used as the heat transfer fluid The system shall be non pressurized capped at at mospheric on the day of installation or shall be vented to atmosphere A length of uninsulated copper tube no less than nominal diameter shall be used at the hot outlet and cold inlet of the solar collector s for a distance of no less than three feet 3...

Page 13: ...e System out lined below All vertical piping between the storage tank and the collector shall be supported at each story or at maxi mum intervals of ten feet 10 Horizontal runs shall be sloped to drain minimum 2 slope and supported every five feet 5 to prevent sagging Roof runs shall be secured and supported providing at least 1 1 2 inches clearance from roof Pipe supports shall be con structed fr...

Page 14: ...ector Sensor Placement The collector sensor shall be located on the solar loop return line as close to the collector as possible Sensors are typically accurate to 1 2 F if properly installed and weatherized The collector probe sensor shall be at tached to the SunEarth collector header pipe either with a stainless steel hose clamp or by inserting the probe sensor into a thermal well in contact with...

Page 15: ...lumbing is required to provide for the isolation of the solar storage tank from the city cold water supply line by means of an isolating ball valve The differential temperature controller shall have a screen readout to show temperatures of the collector and storage tank Otherwise line thermometers shall be installed in the collector supply and return lines to allow for a simple diagnostic check of...

Page 16: ... concrete slab in order to prevent moisture damage to the base of the tank and reduce the heat loss to the floor The tank should be raised off the floor on a pad 4 10 Choosing and Installing the Drainback Res ervoir SunEarth CopperStorTM copper drainback tanks are available in 2 5 5 7 5 and 10 gallon capacities Stain less steel drainback tanks are available in 10 15 and 20 gallons Small glass line...

Page 17: ...illing the System Once the components have been plumbed it is time to fill the solar storage and collector loop with water as follows 4 14 1 STEP 1 Flush and Fill the potable loop with water Close potable flushing combination valves COMPONENTS 24 36 Fill the solar tank with wa ter and check that there are no leaks on the potable side of the system Do this by opening the cold water isolation ball v...

Page 18: ...lso have been visual ly inspected for leaks and the solar loop piping has been cleaned and charged Having successfully com pleted these tasks it is time to set your system to run automatically Set the SunEarth control to the ON position Listen until you can hear water flowing through the solar loop return piping from the collector Place your ear next to the pump and listen for signs of cavitation ...

Page 19: ...ons in excess of sixty days Remember to reset the SunEarth control to the AUTO position upon your return and check the system for proper operation and draining by monitoring the water levels with the pump on and off 9 MAINTENANCE AND TROUBLESHOOTING The following simple procedures are intended to opti mize the performance of your Torrent Drainback solar water heating system and also to extend the ...

Page 20: ...e pump is running and the controller displays questiona ble temperatures at the collector or tank i e 180ºF tank and 45ºF collector check both sensors using a resistance meter to see if they are correctly calibrated If you find a defective sensor replace it immediately 9 10 Auxiliary Electric Element not Operating If the weather is poor and the auxiliary heating ele ment will not fire the bright r...

Page 21: ...d by the plumbing code on water heaters Will automatically release and dump water at either 150 PSI of pressure or 210 F in temperature 21 Mixing Valve Automatically blends hot water from the solar storage tank with incoming city cold wa ter to an acceptable set point A mixing valve must be installed on every Torrent Drainback solar water heat ing system The mixing valve may include and integral c...

Page 22: ...he system is not circulating pump stopped should such that the drainback tank not less than 75 full When the system is circulating pump running the water level in the drainback tank should be not less than 25 full The drainback tank should never be pumped dry in normal operation as this may result in damage to the circulator pump ...

Page 23: ...pire Chrome EC 21 EC 24 EC 32 EC 40 EC 24 0 75 EC 32 0 75 EC 40 0 75 EC 24 1 5 EC 32 1 5 EC 40 1 5 SunEarth SunBelt SB 24 0 75 SB 32 0 75 SB 40 0 75 SunEarth Imperial Chrome IC 32 IC 40 SunEarth Imperial Selective IS 32 IS 40 SunEarth ThermoRay TRB 32 TRB 40 Make Series SunEarth SolarStrut RexRack Flush Mount Kit Universal Tilt Kit Landscape Rack Make Series Model Numbers SunEarth SunEarth SU80U 1...

Page 24: ...ervoir Make Series Model Numbers AIC L Line LA14 10 Make Series Model Numbers SunEarth CopperStor DB 2 5 DB 5 DB 7 5 DB 10 SolarH2OT DBT DBT 10 SS DBT 15 SS DBT 20 SS Rheem Energy Miser 81VP6S 81VP15S 81VP10S 81VP20S A O Smith ProMax EJC 6 EJC 10 EJC 20 Or Approved Equal ...

Page 25: ...e brass or stainless steel construction Maximum working temperature shall be no less than 200 F and maximum working pressure shall be no less than 125 psi Three Way Valves Optional Three Way valves shall be of bronze brass or stainless steel construction Maximum working tem perature shall be no less than 200 F and maximum working pressure shall be no less than 125 psi Boiler Drains A K A Charge Va...

Page 26: ...rating tem perature of not less than 220o F and maximum working pressure of not less than 125 psi Pipe Insulation Pipe insulation shall have a maximum operating temperature of no less than 220o F All pipes shall be insulated to R2 6 or greater typically this will require a wall thickness of or greater When located in exposed areas pipe insulation shall be protected with a UV resistant coating or j...

Page 27: ... WHENEVER THE CIRCULATION PUMP SHUTS OFF WHEN PROPERLY INSTALLED AND OPERATED THE SYSTEM IS PROTECTED TO TEMPERATURES AS LOW AS 50 F VALVE NO 8 COLD WATER SUPPLY ISOLATION VALVE THIS VALVE IS NORMALLY OPEN AND ALLOWS POTABLE WATER TO FILL THE SOLAR STORAGE TANK WHEN CLOSED THE SOLAR STORAGE TANK IS ISOLATED FROM THE PRESSURIZED CITY COLD WATER SUPPLY LINE PIPING BOILER DRAIN NO 11 SYSTEM FILL DRAI...

Page 28: ...EED TO SOLAR TANK ISOLATION VALVE THIS VALVE IS NORMALLY OPEN WHEN CLOSED IN CONJUNCTION WITH VALVE NO 6 IT WILL ISOLATE THE SOLAR STORAGE TANK FROM THE POTABLE WATER SYSTEM VALVE NO 6 HOT OUTLET FROM SOLAR TANK ISOLATION VALVE THIS VALVE IS NORMALLY OPEN WHEN CLOSED IN CONJUNCTION WITH VALVE NO 7 IT WILL ISOLATE THE SOLAR STORAGE TANK FROM THE POTABLE WATER SYSTEM VALVE NO 5 SOLAR TANK BYPASS VAL...

Page 29: ...APPENDIX F ...

Page 30: ...APPENDIX F ...

Page 31: ... 6 1 3 1 1 1 1 0 9 1 3 1 3 2 3 1 6 1 8 1 6 1 5 2 4 1 6 5 2 3 2 1 8 2 3 2 1 7 3 4 2 30004026 30004025 30004024 30004023 30004022 30004021 30004020 30004019 30004018 30004017 30004016 30004015 30004014 30004013 30004012 30004011 30004010 30004009 30004008 30004007 30004006 30004005 30004004 30004003 30004002 30004001 30004000 30003999 30003998 30003997 30003996 30003995 C2 80 120 TLG C2 64 120 TLG C...

Page 32: ...________ System Information Model Number ___________________________________________ Date Purchased __________________________________________ Collector Serial Number ____________________________________ For Service and Repair Contact ______________________________ Comments ______________________________________________ ________________________________________________________ _____________________...

Page 33: ...8425 Almeria Avenue Fontana CA 92335 Phone 909 434 3100 Fax 909 434 3101 Email info sunearthinc com www sunearthinc com Revised 3 17 2014 ...

Reviews: