SPECIAL INSTRUCTIONS FOR CONNECTION TO FORCED AIR SYSTEM.  

READ THESE INSTRUCTIONS BEFORE COMMENCING INSTALLATION. 

  

 

Suncourt® Airiva™ 

Heat Recovery Ventilator 

The Airiva deserves its own ducts; forced air system connection is a distant second choice only. 

The way to avoid this complicated installation is to run the forced air system fan 24 hours per day, every day of 

the year. (Set thermostat to Fan-On). Balance your system and adjust the Airiva to the recommended airflow in 

CFM by closing the two manual dampers the correct amount and securely locking them in that position. You 

will not need motorized dampers. Follow the instructions as they pertain to the manually adjustable dampers 

only. 

REMEMBER: THE FORCED AIR SYSTEM FAN MUST RUN 24/7 

FAILURE TO INSTALL AN ACTIVE DAMPER SYSTEM WHEN CONNECTING TO A FORCED AIR 

DUCT CAN: 

• Cause excessive airflow through the Airiva. 
• Reduce the efficiency from about 70% to less than 10%. 
• Allow raw outside air to enter the home in great volume, resulting in much higher utility bills. 
• Cause excessive water collection inside the Airiva. Normally no water will collect in the Airiva except on very 
high outside humidity days (85% or higher and an indoor air-conditioned temperature of less than 80º F or 27º 
C.) 
• The Airiva heat exchanger core will accumulate an excessive amount of dust and dirt as a result of  
excessive airflow.  

Connecting the Airiva to the air supply and air return ducts of the forced air system requires a good 
understanding of airflow dynamics and the following supplies and equipment: 

Tools and Parts to be field supplied: 

1. Motorized electric airflow dampers Suncourt part ZO106. Two required.  
2. Manual airflow control dampers for 6” duct. Two required. 
3. Airflow measuring equipment. i.e.  
(a) Probe Mass Airflow Sensor or insert station using a moving vane, and/or 
(b) Electronic or equivalent indicator calibrated in FPM or CFM, and/or 
(c) Airflow Collar, and/or 
(d) Pitot Tubes and Magnehelix, and/or 
(e) Mechanical or Electronic Manometer. 

Follow the manufacturer’s instructions and use their charts for the equipment of your choice.

 

4. Low voltage 18 Gauge bell wire, wire connectors and ties. 
5. Calibration Control for dampers (An adjustable damper stop). Suncourt Part: CC100. Two required. 

Summary of Contents for Airiva

Page 1: ... protection follow all instructions and adhere to applicable safety building and electrical codes WARNING Install this product inside a building or dwelling only WARNING Do not operate this product without ductwork or approved grilles being installed at the fan openings to prevent contact with the fans Contact with the operating fans will cause serious injury WARNING Do not install this product wh...

Page 2: ...iriva you should install the drain You will need to make a 5 8 diameter hole in the bottom of the Airiva at the lowest point The Airiva deserves its own ducts forced air system connection is a distant second choice only STANDARD DUCT CONNECTIONS The fresh outside air intake and stale air exhaust ducts should be kept as short as possible On the outside of your home you will need to install hoods to...

Page 3: ...ve the 2 5 16 hex head screws from the fan mounting bracket and remove the mounting brackets Flip the fan around and re secure it with the 2 mounting brackets and screws Re connect the quick connectors and the airflow direction change is complete Figure 2 displays the duct connections if the stale air fan is reversed and Figure 3 shows the duct connections if the fresh air fan is reversed Please n...

Page 4: ...used with a 6 24 VAC damper This damper will be installed in a T fitting on the fresh air intake side of the Airiva When the fresh air to the house is below 45 degrees F 4 degrees C it will open the damper allowing some warm house air to mix with the incoming cold fresh air This allows for an uninterrupted supply of fresh air while avoiding freezing of the unit s core The Suncourt ZO106P Zone Damp...

Page 5: ...Place each plate alternating the airflow channels on each layer Lock the top plate in place with the metal rods being careful not to bend them Clean the screens of the outside vents as necessary ...

Page 6: ......

Page 7: ...bills Cause excessive water collection inside the Airiva Normally no water will collect in the Airiva except on very high outside humidity days 85 or higher and an indoor air conditioned temperature of less than 80º F or 27º C The Airiva heat exchanger core will accumulate an excessive amount of dust and dirt as a result of excessive airflow Connecting the Airiva to the air supply and air return d...

Page 8: ...stale air These motorized dampers are in addition to two manual dampers to be installed in the same ducts for airflow balancing when the forced air system is NOT operating The manual dampers must be balanced first before balancing the motorized dampers The balancing of the manual dampers must be performed when the main forced air system is not operating These manual dampers may be installed either...

Page 9: ... running You should find this connection location on the wiring diagram inside the enclosure cover of your furnace and or in the furnace installation manual You may install the stud mount transformer in one of several knockouts on your furnace The primary connections will be inside the furnace for safety Connect the secondary 24 VAC power to both ZoneMaster motorized dampers in parallel Never conn...

Page 10: ... return air duct 14 Once these two dampers have been initially calibrated repeat the calibration for both dampers since the position of one damper may somewhat affect airflow through the other 15 When you are satisfied that both airflows are within specification tightly secure the Calibration Control wing nuts and instruct the customer to never alter these calibrated settings YOU WILL HAVE TWO MAN...

Page 11: ...t apply to defects resulting from alteration abuse accidental damage unauthorized repair or misuse of the unit c a defective unit must be returned prepaid with proof of purchase after obtaining a return good authorization from Suncourt Inc The unit must be returned in the original packaging and packaged as per enclosed instructions This warranty is given in lieu of all other warranties guarantees ...

Page 12: ...nufacturer reserves the right to change product specifications without notice Airiva is a Trade Mark of Suncourt Inc SUNCOURT INC P O Box 40 500 West Second Avenue Durant IA 52747 0040 USA 1 800 999 FANS ...

Reviews: