Chapter 2
Sun Storage 2500-M2 Arrays Specifications
7
Environmental Requirements
This section describes the environmental conditions that are prerequisite to installing
the unit, and heat conditions that are generated by normal operation of the unit.
lists the environmental conditions in which the array is designed to
operate.
Humidity
lists the relative humidity ranges of the controller tray.
TABLE 2-4
Controller Tray Temperature
*
* If you plan to operate a system at an altitude between 3280 feet to 9842 feet (1000 meters to 3000 meters) above
sea level, lower the environmental temperature 3.3˚F (1.7˚C) for every 3280 feet (1000 meters) above sea level.
Parameter
Requirement
Operating range (both cabinet and subsystem)
50˚F to 104˚F (10˚C to 40˚C)
Maximum rate of change
50˚F (10˚C) per hour
Storage range
14˚F to 122˚F (–10˚C to 50˚C)
Maximum rate of change
59˚F (15˚C) per hour
Transit change
–40˚F to 140˚F (–40˚C to 60˚C)
Maximum rate of change
68˚F (20˚C) per hour
TABLE 2-5
Humidity (noncondensing)
Parameter
Specification
Operating range (both cabinet and
subsystem)
20% to 80% (noncondensing)
Storage range
10% to 90%
Transit range
5% to 90%
Operating gradient
50˚F (10˚C) per hour maximum
Storage gradient
59˚F (15˚C) per hour maximum