Sun Oracle Netra X4250 Site Planning Manual Download Page 6

2

Sun Netra X4250 Server Site Planning Guide • May 2010

Clearance for Service Access

These are the minimum clearances needed for servicing the server.

Environmental Specifications

These are the environmental specifications for the AC and DC versions of the server.

Description

Specification

Clearance, front of server

36 inches (91 cm)

Clearance, rear of server

36 inches (91 cm)

Specification

Operating

Nonoperating

Ambient temperature

*

41˚F to 104˚F (5˚C to 40˚C) up to 6000
feet (1829 meters)

–40˚F to 158˚F (–40˚C to 70˚C)

Relative humidity

10% to 90% noncondensing, short term
25˚F to 113˚F (-5˚C to 55˚C)
5% to 90% noncondensing, but not to
exceed 0.024 kg of water per kg of dry
air (0.053 lbs. water/2.205 lbs. dry air)

Up to 93% noncondensing 100.4˚
(37.7˚C) maximum wet bulb

Elevation (Sun requirement)

Maximum 9840 feet (3000 meters) at
104˚F (40˚C)

Maximum 39370 feet (12000
meters)

Elevation (NEBS requirement)

-200 feet to 5900 feet (-60 meters to 1800
meters) at 104˚F (40˚C)
5900 feet to 13100 feet (1800 meters to
4000 meters) at 86˚F (30˚C)

Vibration

DC servers: 0.1G, 5-100 Hz, 0.1 Oct/min
AC servers: 0.1G (x,y axes); 0.15G (z
axis), 5-500 Hz, 1 Oct/min

DC servers: 0.1G, 5-100 Hz, 0.1
Oct/min
AC servers: 0.25G (x,y axes); 0.5G
(z axis), 5-500 Hz, 1 Oct/min

Shock

DC servers: Operating 30 m/s2, 11msec
half-sine
AC servers: 3G, 11msec half-sine

DC servers: Operating 30 m/s2,
11 msec half-sine
AC servers: 1 in. roll off front to
back, 0.5 in. roll off side to side,
20 mm step-up

Seismic

AC server only: Zone 4

Not applicable

Summary of Contents for Netra X4250

Page 1: ...Sun Netra X4250 Server Site Planning Guide Part No 820 4053 12 May 2010 Revision A...

Page 2: ...tellectuelle Ils sont conc d s sous licence et soumis des restrictions d utilisation et de divulgation Sauf disposition de votre contrat de licence ou de la loi vous ne pouvez pas copier reproduire tr...

Page 3: ...e Requirements 3 Additional Power System Information 3 Changing Sun Servers From AC to DC Input or From DC to AC Input 4 Agency Compliance Specifications 4 Operating Environment 5 Electrical Power 5 A...

Page 4: ...iv Sun Netra X4250 Server Site Planning Guide May 2010...

Page 5: ...ance Guide 820 4054 and the Important Safety Information for Sun Hardware Systems 821 1590 that came with your server Physical Specifications The following are the physical specifications for the serv...

Page 6: ...24 kg of water per kg of dry air 0 053 lbs water 2 205 lbs dry air Up to 93 noncondensing 100 4 37 7 C maximum wet bulb Elevation Sun requirement Maximum 9840 feet 3000 meters at 104 F 40 C Maximum 39...

Page 7: ...g the positive and negative inputs to the power supplies of a DC input system will not cause damage However the power supplies with reversed input will not operate The inputs to a power supply are iso...

Page 8: ...from the agency approved manufacturing site Agency Compliance Specifications The server complies with the following specifications Category Relevant Standards Safety UL CSA 60950 1 EN60950 1 IEC60950...

Page 9: ...ing in the operating environmental limits presented in Environmental Specifications on page 2 Operating computer equipment in extremes of temperature or humidity increases the failure rate of hardware...

Page 10: ...p below 30 Airflow Considerations Ensure unobstructed airflow through the chassis The server uses internal blowers that can achieve a total airflow of 120 CFM 3 4 m3 in normal operating conditions Ens...

Page 11: ...The acoustic noise emissions on the server are as follows Declared noise emissions are in accordance with ISO 9296 standards Calculating Heat Dissipation To calculate the heat generated by a server so...

Page 12: ...Site Planning Guide May 2010 Caution To maintain NEBS compliance the network management NET MGT Ethernet port and the RJ 45 serial management SER MGT port must use shielded cables and both ends of the...

Reviews: