Chapter 7
Service
7-17
7.2.10
Caution –
The disk drive backplane is not a hot-plug item. You must remove power
from the disk array before replacing the disk drive backplane.
1. Power off the disk array.
2. Disconnect the power cable.
3. Remove the disk drives (see Section 7.2.1).
4. Remove the door and panel assembly (see Section 7.2.5).
5. Use the flat-head screwdriver to release both lower disk drive guides (
).
FIGURE 7-14
Releasing a Lower Disk Drive Guide