Chapter 2
Cabinet and Environmental Specifications
19
Thermal loads increase as new equipment is installed, and the cooling capability of
the enclosed cabinet needs to scale as well. Fan packs, which force ambient air from
the front of the cabinet through the back of the cabinet enclosure, aid the internal
equipment fans in removing heat from the array.
Power Requirements
The AC power sources must provide the correct voltage, current, and frequency
specified on the Sun StorageTek 6540 Array model and serial number label. A typical
cabinet is expected to run within the limits shown in
.
TABLE 2-4
Cabinet AC Power Requirements
Parameter
Requirements
Nominal voltages
200 to 240 VAC
Operating voltage
180 to 240 VAC
Frequency range
47 to 63 Hz
Current
32A (2X 16A) maximum
AC power plug
NEMA L6-20P (North American)
IEC 309 16A 3 Position (International)
AC power receptacle
NEMA L6-20R (North American)
IEC 309 16A 3 Position (International)
Power cords
Redundant and independent power sources are highly
recommended to avoid a loss of power to the whole array. Use
power cords in pairs to separate power circuits whenever possible.
Summary of Contents for StorageTek 6540
Page 6: ...vi Sun StorageTek 6540 Rack Ready Site Preparation and Installation Support Guide July 2006 ...
Page 18: ...6 Sun StorageTek 6540 Rack Ready Site Preparation and Installation Support Guide July 2006 ...
Page 34: ...22 Sun StorageTek 6540 Rack Ready Site Preparation and Installation Support Guide July 2006 ...
Page 42: ...30 Sun StorageTek 6540 Rack Ready Site Preparation and Installation Support Guide July 2006 ...
Page 46: ...34 Sun StorageTek 6540 Rack Ready Site Preparation and Installation Support Guide July 2006 ...