14
d7
Defrost stop temperature
0
℃
~ 50
℃
12
℃
℃
/
℉
32
℉
~122
℉
d8
Dripping time
0~60
0: Disabled
2
min
d9
Delay time for displaying the
cabinet temperature after defrost
0~90
10
min
d10
Defrost start delay
0~60
0: Disabled
10
min
d11
Defrost mode
0: Electric defrost
1: Hot gas defrost
0
/
F1
Fan working mode
0: Fan and compressor run or stop
simultaneously;
1: Fan runs continuously and stops
during defrost;
2: Fan runs continuously and stops
during defrost and dripping;
3: Fan runs continuously, stops during
defrost and delays after defrost;
4: Fan is controlled by defrost sensor
temperature, and stops during defrost.
3
/
F2
Fan start delay after the controller
is energized
0~60
3
min
F3
Fan delay time after defrost
0~60
0: Disabled
2
min
A1
Duty cycle mode in the event of a
faulty cabinet sensor
0: Disable
1: Enable
1
/
A2
Compressor off time in duty cycle
mode
1~60
5
min
A3
Compressor on time in duty cycle
mode
1~60
30
min
A4
Buzzer beep
0: Disable
1: Enable
1
/
A5
Low alarm temperature(cabinet)
-50
℃
~ High alarm temperature
(cabinet)
-10
℃
℃
/
℉
-58
℉
~ High alarm temperature
(cabinet)
A6
High alarm temperature(cabinet)
Low alarm temperature(cabinet) ~ 85
℃
24
℃
℃
/
℉
Low alarm temperature(cabinet) ~ 185
℉
A7
Alarm delay
0~60
20
3min
A8
Alarm delay after switch-on of the
device
0~60
40
3min
A9
High alarm offset
1
℃
~30
℃
10
℃
℃
/
℉
1
℉
~ 60
℉
A10
Low alarm offset
1
℃
~30
℃
5
℃
℃
/
℉
1
℉
~ 60
℉
A11
Cabinet temperature alarm
0: Absolute temperature point
1: Temperature set-point + alarm offset
0
/