8  Troubleshooting

34

 

LED Operator Display

Fault Name

EF0

External Fault Input from PROFIBUS-DP Option
The alarm function for an external device has been triggered

Cause

Possible Solution

An external fault is being sent from 
the upper controller (PLC).

Remove the cause of the external fault

• Reset the external fault input from the upper controller (PLC) device

Problem with the upper controller 
(PLC) program.

Check the program used by the upper controller (PLC) and make the 
appropriate corrections

LED Operator Display

Fault Name

oFA00

PROFIBUS-DP Option Fault (Port A)
PROFIBUS-DP Option is not properly connected

Cause

Possible Solution

Non-compatible option connected to 
the drive.

Connect an option that is compatible with the drive

LED Operator Display

Fault Name

oFA01

PROFIBUS-DP Option Fault (Port A)
PROFIBUS-DP Option is not properly connected

Cause

Possible Solution

Problem with the connectors between 
the drive and PROFIBUS-DP Option.

Turn the power off and check the connectors between the drive and 
PROFIBUS-DP Option.

LED Operator Display

Fault Name

oFA03

PROFIBUS-DP Option Fault (Port A)
PROFIBUS-DP Option self-diagnostics error

Cause

Possible Solution

PROFIBUS-DP Option hardware 
fault.

Replace the PROFIBUS-DP Option.

LED Operator Display

Fault Name

oFA04

PROFIBUS-DP Option Fault (Port A)
PROFIBUS-DP Option Flash write mode

Cause

Possible Solution

PROFIBUS-DP Option hardware 
fault.

Replace the PROFIBUS-DP Option.

Summary of Contents for DeviceNet HF-520 Series

Page 1: ...Manual Type SI P3 V H Manual NOTICE 1 Make sure that this installation manual is delivered to the end user of inverter unit 2 Read this manual before installing or operating the inverter unit and stor...

Page 2: ...t liability is assumed with respect to the use of the information contained herein Moreover because Sumitomo is constantly striving to improve its high quality products the information contained in th...

Page 3: ...4 2 PRODUCT OVERVIEW 10 3 RECEIVING 11 4 PROFIBUS DP OPTION COMPONENTS 12 5 INSTALLATION PROCEDURE 17 6 PROFIBUS DP OPTION DRIVE PARAMETERS 26 7 PROFIBUS DP OPTION DATA AND I O MAPS 28 8 TROUBLESHOOTI...

Page 4: ...ion all controls should be designed to detect faults dynamically and fail safely under all circumstances All systems or equipment designed to incorporate a product manufactured by Sumitomo must be sup...

Page 5: ...his book Read this manual first The installation manual is packaged with the PROFIBUS DP Option and contains a basic overview of wiring settings functions and fault diagnoses Inverter HF 520 Series Op...

Page 6: ...the drive This guide provides basic programming and simple set up and adjustment Drive HF 520 Series PROFIBUS DP Option HF 520 Series Option PROFIBUS DP SI P3 V H STOP Hz Hz A V Freq Reference FWD RE...

Page 7: ...ual and local codes The following conventions are used to indicate safety messages in this manual Failure to heed these messages could result in serious or possibly even fatal injury or damage to the...

Page 8: ...notice to improve the product and or the manual DANGER Heed the safety messages in this manual Failure to comply will result in death or serious injury The operating company is responsible for any inj...

Page 9: ...ad manual before installing Wait 5 minutes for capacitor discharge after disconnecting power supply To conform to requirements make sure to ground the supply neutral for 400V class Risk of electric sh...

Page 10: ...on between systems and peripherals at a field level This PROFIBUS DP Option connects a drive to a field network using the PROFIBUS DP protocol PROFIBUS DP is included into the European Fieldbus Standa...

Page 11: ...on properly contact your supplier Contents and Packaging Table 1 Contents of Package Tool Requirements Note Tools required to prepare PROFIBUS cables for wiring are not listed in this manual Descripti...

Page 12: ...Option and are packaged separately in the box H Nameplate B LED BF red I Function Earth cable connection FE C Option cover J Mounting clip D LED ERR red K Cable 1 E LED RUN green L Through hole for ca...

Page 13: ...4 PROFIBUS DP Option Components 13 Dimensions The installed PROFIBUS DP Option adds 27 mm 1 06 in to the total depth of the drive Figure 3 Figure 3 Figure 3 Dimensions 27 mm 1 06 in...

Page 14: ...le 2 Communication connector 9 pin D SUB PROFIBUS Connector Pin Signal Description 1 Shield Connected to the metal shell no direct FG connection 2 3 RxD TxD P Receive Transmit data line B red 4 CNTR P...

Page 15: ...ormal operation Drive and PROFIBUS DP Option are properly connected COMM Communication Status Green ON Communication connected Normal send receive between PROFIBUS DP Option and PROFIBUS DP master OFF...

Page 16: ...ess Cycle power to the drive If the LED status does not change replace the PROFIBUS DP Option Check the node address setting in the drive parameter F6 10 Waiting for data from the master device Waitin...

Page 17: ...k Hazard Do not remove option board cover while the power is on Failure to comply could result in death or serious injury The diagrams in this section may include option units and drives without cover...

Page 18: ...urther damage to the equipment Do not connect or operate any equipment with visible damage or missing parts Do not use unshielded cable for control wiring Failure to comply may cause electrical interf...

Page 19: ...cting both ends of the network If the connector is reversed then communication will not be possible between devices Most connectors have arrows indicating the input and output sides Terminating resist...

Page 20: ...ion Cable to EN50170 pin numbers for a 9 pin D sub connector Bus termination ON incoming and outgoing cables not connected Bus termination OFF incoming and outgoing cables connected Outgoing Cable Inc...

Page 21: ...he drive DANGER Electrical Shock Hazard Do not connect or disconnect wiring while the power is on Failure to comply will result in death or serious injury Before installing the PROFIBUS DP Option disc...

Page 22: ...Figure 10 Figure 10 Ground Cable Note Cover removal for certain larger models with a Terminal Cover Single Phase 200 V Class HF520S A75 to 2A2 Three Phase 200 V Class HF5202 1A5 to 7A5 Three Phase 400...

Page 23: ...om the drive ground terminal to the PROFIBUS DP Option ground When wiring the PROFIBUS DP Option pass the ground cable through the inside of the drive bottom cover then pass the ground cable into the...

Page 24: ...BUS DP dedicated cables that fulfill the specifications in Table 5 For more information on cables refer to the PROFIBUS DP website at http www profibus com Cable Requirements Table 5 Communication Cab...

Page 25: ...able 6 Cable Length GSD Files For easy network implementation of drives equipped with a PROFIBUS DP Option a GSD file can be obtained from Japan http www shi co jp ptc Communication speed kbps Distanc...

Page 26: ...Ramp to Stop 1 Coast to Stop 2 Fast Stop 3 Alarm Only 2 Default 1 Range 0 to 3 F6 02 External Fault Detection Conditions EF0 Sets the condition for external fault detection EF0 0 Always detected 1 Det...

Page 27: ...the PROFIBUS DP network set b1 02 to 3 To control the frequency reference of the drive via the PROFIBUS DP network set b1 01 to 3 2 If F6 03 is set to 3 then the drive will continue to operate when an...

Page 28: ...fter being received by the option MEMOBUS Modbus Message MEMOBUS Modbus message data is transferred to the drive using MEMOBUS Modbus messages All drive parameters and data can be accessed through MEM...

Page 29: ...to Master Device Byte Description Byte Description 0 Operation Command High Byte 0 Drive Status High Byte 1 Operation Command Low Byte 1 Drive Status Low Byte 2 Frequency Reference High Byte 2 Motor...

Page 30: ...Data 4 High Byte 27 MEMOBUS Modbus Data 4 Low Byte 27 MEMOBUS Modbus Data 4 Low Byte 28 Reserved 28 Reserved 29 29 30 30 31 Handshaking Register 31 Handshaking Register 1 To select drive analog output...

Page 31: ...2 Frequency Reference High Byte 2 Motor Speed High Byte 1 3 Frequency Reference Low Byte 3 Motor Speed Low Byte 1 4 MEMOBUS Modbus Function Code 4 MEMOBUS Modbus Function Code 5 MEMOBUS Modbus Starti...

Page 32: ...ZSW HSW and HIW These registers are not mapped directly to drive registers PPO type 1 8 octets PKW 4 octets PZD PPO type 2 8 octets PKW 12 octets PZD PPO type 3 4 octets PZD PPO type 4 12 octets PZD...

Page 33: ...troller CPU stopped Did a momentary power loss interrupt communications Table 11 Fault Display and Possible Solutions LED Operator Display Fault Name bUS PROFIBUS DP Option Communication Error After e...

Page 34: ...use Possible Solution Non compatible option connected to the drive Connect an option that is compatible with the drive LED Operator Display Fault Name oFA01 PROFIBUS DP Option Fault Port A PROFIBUS DP...

Page 35: ...operation command bit F is set to 1 a PPO type data format is used the the control word STW bit 3 is set to 0 Set either of the bits depending on which data format is used No output LED Operator Disp...

Page 36: ...bytes outputs 16 bytes Extended data 2 High speed I O data inputs 4 bytes outputs 4 bytes MEMOBUS Modbus message inputs 8 bytes outputs 8 bytes Basic data High speed I O data inputs 6 bytes outputs 6...

Page 37: ...at is caused by 1 Installation connection combination or integration of the Product in or to the other equipment or machine that rendered by any person or entity other than the Seller 2 Insufficient m...

Page 38: ...No DM2309E 1 0 EA02 Printed 2015 04...

Reviews: