Sulzer ABS CA 461 Installation Manual Download Page 3

3

 81907022A

60 mm  (2,36)

58 mm  (2,28)

108 mm

(4,25)

108 mm (4,25)

35 mm

(1,38)

en

TECHNICAL DATA

2.1 

Technical data CA 461

Leakage sensor voltage

12 VDC

Max sensor current

< 15 µA 

Leakage detection threshold 

< 100 kohm 

Alarm on delay

~10 seconds

Ambient operating temperature

–20 to +50 °C (–4 to +122 °F)

Ambient storage temperature

–30 to +80 °C (–22 to +176 °F)

Degree of protection 

IP 20, NEMA: Type 1

Housing material

PC,PPO, and POM

Mounting

DIN Rail 35 mm 

Humidity

0–95% RH non-condensing

Dimensions

H x W x D: 108 x 35 x 58 mm  

(4.25 x 1.38 x 2.28 in.)

Power supply

110-230 VAC, 50 Hz/60 Hz

Fuse

Max 10 A

Terminal wire size

Use copper (Cu) wire only. 0.2 - 2.5 mm

2

  

flexible core, stripped length 8 mm.

Power consumption 

< 2 W

Max load output  

250 VAC 3 Ampere

Altitude

Max 2000 MASL or 6562 ft. AMSL

Attention

      If the unit is used in a manner not described in this document the protection provided by the equipment may be impaired.

2.2 Dimensions

2.3 Cleaning

How to clean the unit

Power off the unit and only outside/front shall be cleaned by using a dry, soft cloth. A good choice would be the 

microfiber type of cloth. Gently wipe the CA 461 unit front in order not to scratch the overlay. If the dry cloth did not 

completely remove the dirt, do not press harder in an attempt to scrub it off. 

 

If necessary, moisten the cloth by adding a small amount of water with a thin solution of mild detergent and try again. 

Never use detergent with polish or solvent which can have an impact on the plastic surface.