The dryer does not discharge the condensate
–
see the corresponding point.
The hot-gas bypass valve needs to be re-adjusted
–
contact a SULLAIR service technician to have the
nominal setting re-established.
There is a leak in the refrigeration cycle
–
contact a SULLAIR service technician.
Dew point too low.
SR 10-100 - The fan is always ON - the yellow LED of DMC15 electronic instrument is flashing - see
specific point
SR 125-480 - The fan runs continuously
–
the PV pressure switch is defective
–
replace it.
The ambient temperature is too low
–
re-establish the nominal conditions.
The hot-gas bypass valve needs to be re-adjusted
–
contact a SULLAIR service technician to have the
nominal setting re-established.
Extreme pressure
drop in the dryer.
The dryer does not discharge the condensate
–
see the corresponding point.
The dew point is too low
–
the condensate is frozen and blocks the air
–
see the corresponding point.
Check the flexible connection hoses for obstructions.