SPECIFICATIONS

Electrical Requirements

Installation must comply with all applicable electrical codes 
and be properly grounded (earthed). 

International models from the factory designed without a 
transformer require a 220-240 V AC, 50/60 Hz electrical 
supply, fused at the correct rating for the unit. If required 
by local or national codes, the power cord can be easily 
replaced using the power inlet device. 

Locate the electrical supply within the shaded area shown 
in the illustration below. A separate circuit servicing only 
this appliance is required. A ground fault circuit interrupter 
(GFCI) is not recommended and may cause interruption of 
operation.

ELECTRICAL REQUIREMENTS

Power Supply

220-240 V AC, 50/60 Hz

Circuit Breaker

10 amp

Receptacle

grounding-type (earthed)

Plumbing Requirements

Installation must comply with all applicable plumbing codes.

Locate the water supply line within the shaded area shown 
in the illustration below. Connect the water supply line to the 
house supply with an easily accessible shut-off valve. Do 
not use self-piercing valves. The water supply line must not 
interfere with the installation of the anti-tip bracket.

A reverse osmosis system can be used provided there 
is constant water pressure of 2.4–8.3 bar supplied to the 
unit at all times. A copper line is not recommended for this 
application.

PLUMBING REQUIREMENTS

Water Supply 

6.4 mm OD copper line, 

braided stainless steel, or PEX tubing

Water Pressure

2.4–8.3 bar

Excess Water Line for Connection

.9 m

1918 mm

FROM FLOOR

178

mm

E

152

mm

RIGHT SIDE

OF OPENING

 
Electrical supply location

 

76 mm

152

mm

132

mm

RIGHT SIDE

OF OPENING

AREA EXTENDS 13 mm

FORWARD ON FLOOR

 
Water supply location

 

Summary of Contents for ICBPRO3650

Page 1: ...ICB REVISED 5 2019 DESIGN GUIDE NEW PRO REFRIGERATION ...

Page 2: ...ughout this guide dimensions may vary by 3 mm TA B L E O F C O N T E N T S 3 P R O R E F R I G E R AT I O N 4 O V E R A L L D I M E N S I O N S 6 O P E N I N G D I M E N S I O N S 8 E L E C T R I C A L 8 P L U M B I N G 9 S TA N D A R D H A N D L E S 11 S U B Z E R O W A R R A N T Y ...

Page 3: ...on A monument to food preservation equal parts sculpted metal design statement and culinary secret weapon Its vast interior like its bold exterior is crafted of stainless steel Available in 914 mm and 1219 mm widths with a glass or solid door and may be either built in or freestanding ICBPRO3650 ICBPRO3650G ICBPRO4850 ICBPRO4850G ...

Page 4: ...3 mm 657 mm 775 mm 1070 mm 767 mm 949 mm 660 mm 60 mm 914 mm 606 mm 660 mm Overall Dimensions 914 mm MODEL Model ICBPRO3650 ICBPRO3650G SPECIFICATIONS INTERIOR CAPACITY L L ICBPRO3650 521 122 ICBPRO3650G 521 122 SHIPPING WEIGHT KG ICBPRO3650 286 ICBPRO3650G 295 ...

Page 5: ...57 mm 775 mm 1070 mm 767 mm 368 mm 606 mm 781 mm 533 mm 60 mm 1219 mm 606 mm 660 mm Overall Dimensions 1219 mm MODEL SPECIFICATIONS INTERIOR CAPACITY L L ICBPRO4850 530 331 ICBPRO4850G 530 331 SHIPPING WEIGHT KG ICBPRO4850 390 ICBPRO4850G 399 Model ICBPRO4850 ICBPRO4850G ...

Page 6: ... FRAMED CABINETRY W FILLER 89 mm FINISHED RETURN FRAMELESS CABINETRY W 19 mm TYPICAL 89 mm FINISHED RETURN STANDARD OPENING W H D 914 mm Model 902 mm 2127 mm 610 mm 1219 mm Model 1206 mm 2127 mm 610 mm For standard installations the face frame will extend 51 mm beyond cabinetry FLUSH OPENING W H D 914 mm Model 914 mm 2137 mm 660 mm 1219 mm Model 1219 mm 2137 mm 660 mm For flush installations the f...

Page 7: ...89 mm FINISHED RETURN FRAMELESS CABINETRY W 19 mm TYPICAL 89 mm FINISHED RETURN DUAL STANDARD OPENING W H D Two 914 mm Models 1816 mm 2127 mm 610 mm For standard installations the face frame will extend 51 mm beyond cabinetry A dual installation kit is required for this installation DUAL FLUSH OPENING W H D Two 914 mm Models 1829 mm 2137 mm 660 mm For flush installations the face frame will be flu...

Page 8: ...p Receptacle grounding type earthed Plumbing Requirements Installation must comply with all applicable plumbing codes Locate the water supply line within the shaded area shown in the illustration below Connect the water supply line to the house supply with an easily accessible shut off valve Do not use self piercing valves The water supply line must not interfere with the installation of the anti ...

Page 9: ...ss steel pro handles are avail able through an authorized Sub Zero dealer Refer to the chart below for standard handle lengths for PRO models HANDLE LENGTH 914 mm MODEL 1219 mm MODEL Door 703 mm 703 mm Refrigerator Drawer 665 mm 506 mm Freezer Drawer 665 mm 294 mm ...

Page 10: ...ican Kitchens The Fine Art of Kitchen Design Wolf Wolf Design Wolf Gourmet W Design red colored knobs Cove and Cove Design are registered trademarks and service marks of Sub Zero Group Inc and its subsidiaries All other trademarks are property of their respective owners in the United States and other countries ...

Page 11: ...warranty covers all parts and labor to repair or replace under normal residential use these parts that prove to be defective in materials or workmanship compressor condenser evaporator drier and all connecting tubing All service provided by Sub Zero under the above warranty must be performed by Sub Zero factory certified service unless otherwise specified by Sub Zero Inc Service will be provided d...

Page 12: ...SUBZERO COM ...

Reviews: