11.8.4
Signals
SEMOD53803-1 v2
PID-3819-INPUTSIGNALS v5
Table 358:
RANGE_XP Input signals
Name
Type
Default
Description
RANGE
INTEGER
0
Measured value range
PID-3819-OUTPUTSIGNALS v5
Table 359:
RANGE_XP Output signals
Name
Type
Description
HIGHHIGH
BOOLEAN
Measured value is above high-high limit
HIGH
BOOLEAN
Measured value is between high and high-high
limit
NORMAL
BOOLEAN
Measured value is between high and low limit
LOW
BOOLEAN
Measured value is between low and low-low limit
LOWLOW
BOOLEAN
Measured value is below low-low limit
11.8.5
Operation principle
SEMOD52462-4 v5
The input signal must be connected to a range output of a measuring function block
(CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGAPC).
The function block converts the input integer value to five binary output signals
according to
.
Table 360:
Input integer value converted to binary output signals
Measured supervised
value is:
below low-low
limit
between low‐
low and low
limit
between low
and high limit
between high-
high and high
limit
above high-
high limit
Output:
LOWLOW
High
LOW
High
NORMAL
High
HIGH
High
HIGHHIGH
High
11.9
Limit counter L4UFCNT
GUID-22E141DB-38B3-462C-B031-73F7466DD135 v1
Section 11
1MRK 505 384-UEN A
Monitoring
482
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...