Name
Type
Values (Range)
Unit
Description
UnTrigStatCh40
BOOLEAN
-
-
Under level trig for
analog channel 40
activated
OvTrigStatCh40
BOOLEAN
-
-
Over level trig for analog
channel 40 activated
FaultNumber
INTEGER
-
-
Disturbance fault
number
11.6.7
Operation principle
M12155-6 v10
Disturbance report DRPRDRE is a common name for several functions to supply
the operator, analysis engineer, and so on, with sufficient information about events
in the system.
The functions included in the disturbance report are:
•
Event list (EL)
•
Indications (IND)
•
Event recorder (ER)
•
Trip value recorder (TVR)
•
Disturbance recorder (DR)
•
Settings information
Figure
shows the relations between Disturbance Report, included functions
and function blocks. Event list (EL), Event recorder (ER) and Indications (IND)
uses information from the binary input function blocks (BxRBDR). Trip value
recorder (TVR) uses analog information from the analog input function blocks
(AxRADR). Disturbance recorder DRPRDRE acquires information from both
AxRADR and BxRBDR.
Figure 223:
Disturbance report functions and related function blocks
The whole disturbance report can contain information for a number of recordings,
each with the data coming from all the parts mentioned above. The event list
function is working continuously, independent of disturbance triggering, recording
time, and so on. Settings information function contains all the visible settings,
parameter information of components configured in ACT, runtime status and
IEC61850 behavior that is added to the disturbance record header file. These
settings information is recorded in XML format and then grouped for each function
instance in the HDR file. The function, setting names and Enum values are same as
in the HMI and can be translated to the selected HMI language. All setting values
are updated along with the units. If the setting values are related to the global base
value, then the setting value is scaled and updated with corresponding global base
unit. All information in the disturbance report is stored in non-volatile flash
memories. This implies that no information is lost in case of loss of auxiliary
power. Each report will get an identification number in the interval from 0-999.
1MRK 505 384-UEN A
Section 11
Monitoring
Breaker protection REQ650 2.2 IEC
471
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...