6.8.4
Signals
PID-6931-INPUTSIGNALS v1
Table 86:
STBPTOC Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase currents
BLOCK
BOOLEAN
0
Block of function
BLKTR
BOOLEAN
0
Block of trip
RELEASE
BOOLEAN
0
Release of stub protection
PID-6931-OUTPUTSIGNALS v1
Table 87:
STBPTOC Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip
START
BOOLEAN
General start
6.8.5
Settings
PID-6931-SETTINGS v1
Table 88:
STBPTOC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
ReleaseMode
Release
Continuous
-
-
Release
Release of stub protection
I>
5 - 2500
%IB
1
200
Operate current level in % of IBase
Table 89:
STBPTOC Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
tDelay
0.000 - 60.000
s
0.001
0.000
Time delay
Table 90:
STBPTOC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base
Value groups
Section 6
1MRK 505 384-UEN A
Current protection
156
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...