background image

Parameter

CRH

47

Function :

 To view Compressor run 

Hours.

It will display compressor run hours. It's a 
read only parameter.

NO

YES

NO

CCRH

48

Function :

 Clear Compressor Run 

Hours.

If  this  parameter  is  set  to  ‘YES’ 
compressor run hours (CRH) are cleared.

Range

Min 

Max 

   Fact. Set 

Range

Min 

Max 

   Fact. Set 

24

Sr. 

No. 

Parameter setting method

Description of parameters and functions.

Parameter 

Sr. 

No. 

Parameter setting method

Description of parameters and functions.

Parameter 

Parameter

E8

Use UP/DOWN keys to set desired value. 

Example: 

If  this  is  set  to  10  min,  then 

manual defrost for 10 min will take place 
during Coil probe fail.

42

Function :

 Defrost duration during Coil 

probe failure.

To change E8 parameter, 
press the SET key.

1 Min

15 Min

5 Min

Range

Min 

Max 

   Fact. Set 

Range

Min 

Max 

   Fact. Set 

To change PDN parameter, 
press the set key.

PDN
Parameter

45

Range

Min 

Max 

   Fact. Set 

Range

Min 

Max 

   Fact. Set 

DIS

EDEF

DIS

Function :

 To activate Solenoid Valve 

relay.
Use UP/DOWN keys to set desired value. 

Example : 

If this parameter is set to 7 mins 

then,  when  light  is  switched  ON,  after  7 
mins it will be switch OFF automatically.

LD
Parameter

Use UP/DOWN keys to set desired value. 

43

Function :

 To set time delay to switch 

off the light .

To change LD parameter, 
press the SET key.

0 Min

30 Min

7 Min

Range

Min 

Max 

   Fact. Set 

Range

Min 

Max 

   Fact. Set 

Parameter

LSD

Use UP/DOWN keys to set desired value.

44

Function :

 This parameter is used to 

enable / disable light relay ON at door 
open.

To change LSD parameter, 
press the SET key.

DIS

ENB

ENB

Range

Min 

Max 

   Fact. Set 

Range

Min 

Max 

   Fact. Set 

This parameter is used set the time delay 
to automatically switch OFF the light.  If LD 
is set to 0 then this parameter is disabled.

If  this  parameter  is  set  to  Enable  then 
whenever Door get open, the Light Relay 
will be ON.

If  this  parameter  is  set  to  Disable  then 
Light  Relay  will  be  ON/OFF  functioning 
manually and as per LD parameter.

0

9999

0

To change the PW parameter, 
press the set key. 

PW 
Parameter

46

Function :

 To change password.

Use  UP/DOWN  key  to  change  the 
password.

User  can  enter  into  program  mode 
only if correct password is entered. If the 
password is wrong it will show ‘INVALID 
PASSWORD’. 

Range

Min 

Max 

   Fact. Set 

Range

Min 

Max 

   Fact. Set 

ETMP : If this parameter is set to ETMP 
then SV relay will be ON/FF & pump down 
at Set point.

active  only  with  Compressor  except 
Hotgas defrost.

EDEF  :  Pump  down  enable  at  Set  point 
when heater defrost condition occurs.

DIS : Pump down disable and SV relay will

Example :

ETMP : Pump down enable at Set point 
when compressor tripped on Set Point.

EDEF : If this parameter is set to EDEF 
then  SV  relay  will  be  ON/OFF  on  SP  & 
pump  down  only  at  heater  defrost 
condition.

Cont.

23

Changes Suggested by Pradnya,

1. Factory set Value of C-OL for 50.0A CT will change from 25.0A to 30.0A
2. PDN Parameter – DIS : Pump down disabled & SV Relay will active only with Compressor except Hotgas defrost.

Summary of Contents for CRC-2052

Page 1: ......

Page 2: ...Oil Pressure Switch OPS I P Index 02 Index DESCRIPTION PARAMETER Pg No To set Evaporator Fan stop temperature To set Evaporator Restart Delay To set Evaporator Fan status at compressor off To set Evap...

Page 3: ...e compressors from close starts In case of probe error or temperature alarm the instrument signals the event through acoustic signal and by closing the relay contact By pressing the mute key the buzze...

Page 4: ...Set mode Also used as enter key if controller is in Set mode program mode Also used to save changed value Used to enter in manual defrost and to stop defrost if defrosting is ON Used to enter in fault...

Page 5: ...ON OFF ON OFF Flashing ON OFF Flashing ON OFF ON OFF ON OFF OFF ON ON OFF ON OFF ON OFF ON OFF 07 High temperature alarm for Room temperature means room temperature is equal or above the set value of...

Page 6: ...enerate HTAlarm SP 0 5 C 50 0 C 50 0 C Range Min Max Fact Set Message on Display Message on Display 02 P3 Parameter Function To set allowable low temperature limit Example Setting this parameter at Us...

Page 7: ...press the set key To change P5 parameter 04 Function To set room probe calibration 10 0 C 10 0 C 0 0 C Range Min Max Fact Set 11 Sr No Parameter setting method Description of parameters and functions...

Page 8: ...f a power failure P10 Parameter 09 Function To set type of defrost To change the P10 Parameter press the set key Use UP DOWN keys to set desired value HTR HTG HTR Range Min Max Fact Set HTR Heater def...

Page 9: ...e the QFD Parameter press the set key Use UP DOWN keys to set desired value This is the maximum amount of time allowed for Quick Freeze If set to 0 there will be no quick freeze 1hr Example If QFS is...

Page 10: ...10 0 C to 10 0 C may be offset by a degree or so To compensate for this error you may need to add or minus the degrees required to achieve the correct temperature Setting Use UP DOWN keys to set desi...

Page 11: ...mpressor current is greater than 15 0 A then and exist till C2 current sensing delay then C OL fault exists and flash on display Compressor will be tripped on this fault NOTE 20 50A CT option availabl...

Page 12: ...l Mode Use UP DOWN keys to set desired value AUTO Auto mode TON Parameter press the set key To change TON parameter 39 Range Min Max Fact Set Range Min Max Fact Set At room probe fail condition when E...

Page 13: ...er press the SET key 0 Min 30 Min 7 Min Range Min Max Fact Set Range Min Max Fact Set Parameter LSD Use UP DOWN keys to set desired value 44 Function This parameter is used to enable disable light rel...

Page 14: ...unction To set display at power OFF mode Use UP DOWN keys to set desired value OFF Display will show OFF TEMP Display will show Temperature LED Display Will be Blank At power OFF mode power OFF LED wi...

Page 15: ...tion 0 1 C LSV Relay 10A 230vac Resolution 0 1Amp RS485 Connectivity Modbus RTU Protocol Mounting Wall mounting Controller CRC 2052 0 0 Operating Temp 5 C to 50 C non condensing 0 0 Storage temp 20 C...

Page 16: ...w Connection Diagram To set fault recover delay Get to know your Controller 29 Introduction 29 Instruction Manual LVM Line Voltage Monitor Three Phase VMRC 10 3 Introduction VMRC 10 3 is three phase L...

Page 17: ...more than TTD value then only fault is raised and this fault is applicable to Under voltage Over voltage and Unbalance fault i e In case of Phase Loss or Phase sequence fault alarm will come immediate...

Page 18: ...s to set desired value This parameter provided to calibration voltage reading When dsP is L n then it sets calibration for r n Sr No Parameter setting method Description of parameters and functions Pa...

Page 19: ...7 8 9 R 15 17 19 21 Y B N General Specification Under voltage and Over voltage detection Application Voltage and phase sequence monitoring and controlling Connections Screw terminals 2 5sqmm one wire...

Page 20: ...36...

Page 21: ...part of this manual may be reproduced or transmitted in any form or by any means without the prior written permission of the company Notice Disclaimer Warranty This manual its contents remain the sole...

Page 22: ...s Globe Valves Hand Valves Flow Switches Solenoid Valves OUR OTHER PRODUCTS Cold Room Controller Chiller Controller Two Compressors Controller Heating Controller Humidity Controller Pressure Controlle...

Reviews: