Stulz CyberRow DX CRS-042-AR Engineering Manual Download Page 5

5

 

© STULZ USA – All rights reserved  QEWR002G

CYBERROW DX ENGINEERING MANUAL

MODEL

 NOMENCLA

TURE SPE

CIFIC

A

TIONS

Air Cooled Remote Evaporator

(Models CRS - _ _ _ - AR)
The fl oor mounted precision air conditioner system 
shall be a split air cooled evaporator with remote air 
cooled condenser. The evaporator section shall house, 
at a minimum, the evaporator coil, expansion valve, 
compressor, evaporator blower/motor and associated 
electrical and refrigeration components.

DX Water Cooled

(Models CRS - _ _ _-W)
The fl oor mounted precision air conditioner system shall 
be self-contained to include an integral water cooled, 
plate-fi n condenser with factory installed head pressure 
water regulating control valve(s). Condenser (source) water 
shall be provided by a cooling tower or some other remote 
water source.

Head Pressure Control

Head pressure shall be automatically controlled by factory 
installed 2-way, or 3-way water regulating valves rated for 
600 psig w.w.p.

DX Glycol Cooled

(Models CRS - _ _ _ - G)
The fl oor mounted precision air conditioner system shall 
be self-contained to include an integral glycol cooled, 
plate-fi n condenser with factory installed head pressure 
glycol regulating control valve. Condenser (source) glycol 
solution shall be provided via a STULZ model GPS - _ - 
_  remote glycol pump package and F _ S -_  dry cooler 
system.

Glycol Regulating Valve

Head pressure shall be automatically controlled by factory 
installed 2-way, or 3-way, water regulating valve rated for 
600 psig w.w.p.

Summary of Contents for CyberRow DX CRS-042-AR

Page 1: ...1 STULZ USA All rights reserved QEWR002G CYBERROW DX ENGINEERING MANUAL CyberRow DX Row Based Precision Air Handling Units 12kW 33kW 60 Hz DX Air Water Glycol Floor Mounted Systems Engineering Manual...

Page 2: ...tions GLOBAL LEADER From our beginnings in Germany 70 years ago to our expansionthroughouttheworld STULZisalwaysinnovating Today STULZ has seven global production plants and hundreds of sales and serv...

Page 3: ...ING MANUAL Table of Contents Model Nomenclature 4 Model Features 4 Model Nomenclature Speci cations 5 Con gurations 6 Product Features 7 Technical Data 8 10 Electrical Data 11 Sound Data 11 Dimensiona...

Page 4: ...ustry 12 and 24 cabinet widths 3 EC Fans Independently and in nitely adjustable EC fans ensure maximum ef ciency Used in containment open architecture and hot spot reduction applications Adapts to bot...

Page 5: ...nstalled head pressure waterregulating controlvalve s Condenser source water shall be provided by a cooling tower or some other remote water source Head Pressure Control Head pressure shall be automat...

Page 6: ...om IT equipment and prevents from mixing with cool air The front of IT equipment is accessed in the external cold aisle The STULZ CyberRow draws the contained hot air from the hot aisle removes the he...

Page 7: ...dard Dual Power Connection N A N A N A Remote Stop Start Contacts Standard Standard Standard Main Power Switch Standard Standard Standard E MICROPROCESSOR CONTROLLER A C Grouping pLAN Interface Option...

Page 8: ...8 4 5 8 Face Velocity fpm 260 500 500 Compressor Heat pump duty rated Scroll R410A Type Qty Scroll 1 Scroll 1 Scroll 1 Watts Input 3 680 7 090 7 830 Tot Heat of Rej MBH 64 6 124 131 8 Condenser Type R...

Page 9: ...ing 2 Way Water Valve Optional Control Modulating 3 Way Water Valve Compressor Heat pump duty rated Scroll R410A Type Qty Watts Input 2 820 3 940 5 690 7 470 6 290 8 250 Tot Heat of Rej MBH 66 64 128...

Page 10: ...92 98 106 96 Total KW 14 3 15 4 14 0 27 4 29 7 26 8 29 31 28 Sensible 14 3 15 4 14 0 27 4 29 7 26 8 29 31 28 90 FDB 66 1 FWB Entering Air Temperature Total MBH 46 50 45 88 97 88 93 102 91 Sensible 46...

Page 11: ...614 speci es a method for measuring the component of sound intensity that is normal to a measurement surface The measurement surface is chosen to enclose the noise source s so that the sound power lev...

Page 12: ...PIPING CONNECTIONS CONNECTIONS CONDENSATE CONDENSATE CONNECTION CONNECTION 11 6 77 8 42 1 CONDENSATE CONNECTION PIPING CONNECTION POWER CONNECTION AIROUT AIRIN AIR OUT AIR OUT AIR IN AIR IN POWER POWE...

Page 13: ...tandards of quality management to ensure product quality Each system shall be subjected to a complete operational and functional test procedure at the factory prior to shipment CABINET Side access pan...

Page 14: ...Flooded Control AR The air cooled system shall incorporate a low ambient ooded head pressure control The pressure control shall be for year REFRIGERATION SYSTEM All piping and components contained wi...

Page 15: ...ach high voltage circuit shall be individually protected by circuit breakers or manual motor starters on all three phases The blower motor shall have thermal and short circuit protection Line voltage...

Page 16: ...creens PASSWORD PROTECTION Access to the Info Menu Alarms Log and the ability to monitor room conditions shall be allowed without the use of a password Modi cations to the control setpoints shall requ...

Page 17: ...20 ft long remote strip cable type water and leak detector shall be provided for remote eld installation Upon sensing a water leak the normallyclosedwaterdetectorcontrol circuit shall open thereby sh...

Page 18: ...18 QEWR002G STULZ USA All rights reserved CYBERROW DX ENGINEERING MANUAL NOTES...

Page 19: ...19 STULZ USA All rights reserved QEWR002G CYBERROW DX ENGINEERING MANUAL NOTES...

Page 20: ...28918 Legan s Madrid STULZ France S A R L 107 Chemin de Ronde 78290 Croissy sur Seine info stulz fr STULZ S p A Via Torricelli 3 37067 Valeggio sul Mincio VR STULZ CHSPL India Pvt Ltd 006 Jagruti Ind...

Reviews: