Down
Button

To Lock and Unlock The Unit for Programming 

Press the Enter, Up, and 
Down buttons in sequence 
and hold them all down until 
“- - -” is displayed. Hold for 
about 10 seconds until the 
current temperature is dis-
played. This toggles the key-
pad between locked and 
unlocked. 

 

To change the set point 

1.  Hold the Enter button 

down for 3 seconds. 
The display will change 
to show the set point. 
Release the Enter     
button. 

2.  Press the Up or Down 

button until you reach 
the new set point. 

3.  Press the Enter button 

to save the new set-
point. 

 

Note: 

If the Enter button is not pressed after select-

ing the new set point, the new set point is not saved, 
and the control will revert to the original set point. 

 

To Begin a Manual Defrost Cycle 

 

Hold the Defrost button 
down for 3 seconds. 

 

 

To Begin a Deep Freeze Cycle 

 

Press the Enter and Up but-
tons in sequence and hold 
both for 5 seconds. The 
compressor status LED will 
light. 

To Program Values Other Than The Setpoint 

A parameter settings reference page is included in Table 3 
of this bulletin. Filling out the parameter settings before    
programming may be helpful. 

 

1. 

H

old the Enter button down 

for about 10 seconds. The 
display will change to HY. 

2.  Press the Up or Down  button 

until the desired parameter is 
displayed. 

3.  Press the Enter button. The 

parameter’s current value is 
displayed. 

4.  Press the Up or Down  button 

until the desired value is 
shown. 

5.  Press the Enter button to 

save the new value. After 
10 seconds of inactivity, the 
display will return to its       
normal function. 

 

Note: If the Enter button is not pressed after selecting the 
new value, the new value is not saved, and the control will 
revert to using the previous value. 

 

To Run the Self-Test Procedure 

 

Press the Up and Down buttons 
in sequence, and hold for 5     
seconds. 

 

 

IMPORTANT: 

Disconnect loads before beginning        

Self-test procedure. Cycle power to resume normal           
operation.

 

Summary of Contents for Oasis CO2739R

Page 1: ...12 Model CO2739R 27 1 2 L x 39 H x 33 D Includes end panels I Oper Manuals Oasis CO27 L R_99399 pub 888 E Porter Road Muskegon MI 49441 Phone 231 798 8888 Fax 231 798 4960 www structuralconcepts com R...

Page 2: ...REFRIGERATION FUNDAMENTALS REFRIGERATION FUNDAMENTALS SERIAL LABEL LOCATION INFORMATION LISTED TECH INFO SERVICE TROUBLESHOOTING ILLISTRATED PARTS BREAKDOWN PARTS LIST CLEANING SCHEDULE CAREL TEMPERAT...

Page 3: ...n in violation of applicable NEC federal state and local electrical and plumbing codes are not covered by warranty See below compliance guideline WARNINGS This sheet contains important warnings to pre...

Page 4: ...arge self contained units only CAUTION CAUTION LAMP REPLACEMENT GUIDELINES LED lamps reflect specific size shape and overall design Any replacements must meet factory specifications Fluorescent lamps...

Page 5: ...perature The lights should come on at the same time First time lighting may require a short warm up period for the bulbs Slightly dim or a flickering of new bulbs is normal It is recommended that the...

Page 6: ...ut lower edge and remove grille 3 Light Fixture Removal of lamp Rotate lamp 1 4 turn either direction to disengage upper or lower pins contacts from lamp mounting sockets Remove bulb buy applying even...

Page 7: ...lapse the honeycomb to allow it to be pulled out of honeycomb retainer C Pry downward and away from honeycomb retainer Clean honeycomb with warm water and soap solution Submerse if necessary Use brush...

Page 8: ...e the heating wire that prevents condensation on the lamp assembly Wedge the instrument between the honeycomb and the top cap closure end panel Apply pressure to collapse the honeycomb and pry downwar...

Page 9: ...ower decking A finger hole is provided to assist in lifting up and pulling out deck 3 Expansion Valve Access Remove lower decking A finger hole is provided to assist in lifting up and pulling out deck...

Page 10: ...well as regulatory standards to which the case conforms For additional technical information and service see the TECHNICAL SERVICE page in this manual for instructions on contacting Structural Concep...

Page 11: ...s properly secured System is not Operating Check that the utility power is on Check that the MAIN power switch is on Check the circuit breaker box for tripped circuits Temperature Controller Has No Il...

Page 12: ...he case it will take time for the temperature to adjust The temperature will change during defrost mode but will return to normal Check that the case is not in the sun or near a heat or air conditioni...

Page 13: ...13 ILLUSTRATED PARTS BREAKDOWN 4 8 2 6 7 15 13 5 3 14 9 1 17 12 11 10 16...

Page 14: ...Panel 11 Wire Channel 3 End Panel Mirror 12 Rear Grille 4 Air Deflector Glass 13 Temperature Controller 5 Single Pole Switch 14 Fan Motor Evaporator 6 Front Panel 15 Deck Pan 7 Bumper Insert 16 Lamp B...

Page 15: ...ove rear doors and clean with a household or commercial cleaner X Vacuum tub under deck or soap and water if necessary To flush out the tub disconnect power to the case Remove the ABS deck and the fan...

Page 16: ...timeout occur normal operational settings prior to modifications being made will resume 3 If the instrument is switched off before pressing the Prg key all modifications to parameters will be lost Set...

Page 17: ...set reset HACCP alarms reset temp monitoring Summary Table of Alarm and Signals Display Buzzer and Relay Integrated Electronic Microprocessor Controller Read And Save These Instructions Page 2 of 3 Us...

Page 18: ...tor min F 1 250 d6 Display on hold during defrost C 0 2 dd Dripping time after defrost min F 0 15 d 1 Display of defrost probe 1 C F F 5 Select Celsius C or Fahrenheit F flag C 0 1 18 For Case Specifi...

Page 19: ...ut is on Correct problem to reset control A2 Digital input closed for longer than time delay id and digital input iF Option 2 is selected Alarm output is on Correct problem to reset control A3 Digital...

Page 20: ...To Begin a Deep Freeze Cycle Press the Enter and Up but tons in sequence and hold both for 5 seconds The compressor status LED will light To Program Values Other Than The Setpoint A parameter setting...

Page 21: ...by SCC as a result of or in connection with any act omission or use of the Goods by Purchaser its employees or customers or any breach of this Agreement by Purchaser Liabilities shall include all cos...

Reviews: