SERVICE MANUAL 

(v1)

 

 

UL / ULC 

 
 

WATER – HAND PORTABLE 

STORED PRESSURE FIRE EXTINGUISHERS 

Model: SF-PW250 / WBDL-PW250 

 
 
 

 

 

All fire extinguishers should be installed, inspected & maintained in accordance with the National Fire Protection Association (NFPA) 10, 
2007 Edition “Standard for Portable Fire Extinguishers” and the local authorities having jurisdiction. 
 
When installation, inspection or maintenance is required, Strike First Corporation strongly recommends the work to be performed by 
NFPA 10 (2007) certified personnel.  Fire extinguishers are pressure vessels and must be treated with respect and handled with care.  
They are mechanical devices and require periodic maintenance to be sure that they are ready to operate properly and safely. 
 
Strike First Corporation makes O.E.M. parts available to insure proper maintenance.  Substituting O.E.M. parts voids the Strike First 
warranty, as well as the UL & ULC Listings. 

 DO NOT SUBSTITUTE

.     

 
Strike First Corporation does not service, maintain or recharge fire extinguishers.  This manual is published as a guide to assist qualified 
service personnel in the inspection, maintenance and recharge of Strike First fire extinguishers only.  

This service manual should be 

used in conjunction with the appropriate Parts Lists/Pictograms for each unit being serviced.

  No service manual can anticipate 

all the possible malfunctions that may be encountered in the service of fire extinguishers.  Due to the possibility that prior service 
performed on this equipment may have been improperly done, it is extremely important that all warnings, cautions and notes in this 
manual be carefully observed.  Failure to heed these instructions could result in serious injury. 
 
Strike First Corporation assumes no liability for service, maintenance or recharge of fire extinguishers by publishing this service manual. 
 
For installation instructions of Strike First portable fire extinguishers please refer to all of the following:  

1. 

Owner’s Manual - included with the unit 

2. 

NFPA 10 “Standard for Portable Fire Extinguishers – 2007 Edition 

3. 

Local authorities having jurisdiction 

 
For operation instructions on Strike First portable fire extinguishers please refer to one or all of the following: 

1. 

Fire Extinguisher Nameplate/Label 

2. 

Owner’s Manual – included with the unit 

3. 

NFPA 10 “Standard for Portable Fire Extinguishers – 2007 Edition 

4. 

Your local authorized Strike First Distributor 

 
WARNING: 

ALWAYS WEAR EYE PROTECTION WHEN SERVICING PRESSURIZED FIRE EXTINGUSIHERS.

 

 

CAUTION: 

PERSONS EXPECTED TO USE THIS FIRE EXTINGUISHER SHOULD BE TRAINED IN INITIATING ITS 
OPERATION AND IN THE PROPER FIRE FIGHTING TECHNIQUE.

 

 
 

RECHARGE FIRE EXTINGUISHERS IMMEDIATELY AFTER ANY USE 

 
 

H

2

O

STRIKE FIRST 
CORPORATION

WARNING 

 

DO NOT USE THIS EXTINGUISHER ON CLASS C (ENERGIZE ELECTRICAL EQUIPMENT), 
B (FLAMMABLE LIQUIDS) OR D FIRES.   

 

PROTECT FROM FREEZING TEMPERATURES