INIT, RESET AND WATCHDOG FUNCTIONS

INIT Function

The INIT function facilitates access to a device when there is a problem accessing it at its configured IP address. The configured 
username and password are required for INIT access.
The INIT terminal is adjacent to the power terminals. Applying power to the device while the INIT terminal is shorted to the -VS 
terminal causes the device to request a temporary IP address from the DHCP server on the network. If there is no DHCP server on 
the network, the device will temporarily use 192.168.1.174. 
The temporary INIT mode Modbus ID is 245.
Once connected in INIT mode, device network parameters (IP address, subnet mask, etc.) may be changed to conform to the 
requirements for your industrial network. Other parameters may also be modified while INIT mode is active. Once the short (or 
jumper) is removed from the INIT and -VS terminals, the device can be accessed using the user-configured IP address, username, and 
password.

NOTE: If not using DHCP, verify that 192.168.1.174 is not in use on your network and ensure that the 192.168.1.n network is 
accessible to your computer.
To use the INIT function:

•  Before applying power to the device, short the INIT terminal to the -VS terminal.
•  Apply power to the device and connect the RJ45 Ethernet port to your computer.
•  Open a browser and type 192.168.1.174 or the DHCP-assigned address in the address field.
•  Browse through the user interface to view configuration settings and data, or change configuration settings.
•  When all changes are complete and saved, disconnect power from the device.
•  Remove the connection shorting the INIT and -VS terminals.
•  Apply power to the device and access it from a browser using the configured IP address, user name and password.

NOTE: When INIT mode is active, the analog input measurements are not updated.

Hardware Reset to Default

With the device powered and not in INIT mode, push and hold the RESET button located on the front of the device for 5 seconds. 
The green PWR LED will switch off, the yellow STS LED will turn orange and the device will reset.
When the reset procedure is finished, both LEDs will be in the default condition and the following parameters will be set:

• 

IP Address

: 192.168.1.100

• 

Subnet Mask

: 255.255.255.0

• 

Default Gateway

: 192.168.1.1

• 

Modbus Address

: 1

• 

Username

: admin

• 

Password

: password

Watchdog Function

The device is equipped with a Watchdog timer. If enabled, it activates an alarm each time that there is not communication between 
the device and the master for a time greater than that specified.
During this alarm condition the green PWR LED on the front of the device blinks and the “Watchdog Event” coil is forced to 1. 
To exit from the alarm condition, send any command to the device and reset the “Watchdog Event” coil.
NOTE: When the device is switched off the state of the “Watchdog Enable” bit remains stored in EEPROM.

Summary of Contents for SIO-MB04THMS

Page 1: ...Manual Number SIO MB04THMS UG Field I O SIO MB04THMS USER GUIDE Temperature Input Module thermocouple 4 channel in ...

Page 2: ... Type Channel 0 R W 40032 Input Type Channel 1 R W 40033 Input Type Channel 2 R W 40034 Input Type Channel 3 R W 40041 Analog Input 0 Ch0 RO 40042 Analog Input 1 Ch1 RO 40043 Analog Input 2 Ch2 RO 40044 Analog Input 3 Ch3 RO 40050 Break Status RO 41241 Offset Channel 0 R W 41242 Offset Channel 1 R W 41243 Offset Channel 2 R W 41244 Offset Channel 3 R W SUPPORTED MODBUS FUNCTION CODES Function Desc...

Page 3: ...Stride Field I O 2 SIO MB04THMS User Guide 1st Edition PRODUCT LABEL AND WIRING DIAGRAM Terminal block pinouts and wiring diagrams are printed on the side of the module as shown below ...

Page 4: ...each time power is applied to the device to indicate that the device has been switched off or reset With the setting of this bit as 0 by the user and checking its state it is possible to know if a reset of the device has occurred 0 reset not occurred 1 reset occurred This bit must be reset manually Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 Coil 163 162 161 Description Watchdog Event enab...

Page 5: ...red with two implied decimal places for mV inputs For example Input type set as Tc 246 stored in the register indicates 24 6 C Input type set as mV 24656 stored in the register indicates 246 56 mV NOTE When INIT mode is active the analog input measurements are not updated 40050 BREAK STATUS When a break condition is detected e g broken sensor disconnected cable or over temperature the bit correspo...

Page 6: ...slightly Enter the Username and Password Default username admin Default password password Click Login to access the device as follows Note that all pages include a Logout button to quit and return to the login page The device interface includes five configuration categories as shown by the navigation menu on the left of the screen on the next page Hovering over a navigation button will display a t...

Page 7: ... gateway A default gateway allows this device to communicate with devices on another subnet Socket Timeout set the timeout time in minutes the device will close its TCP connection if it does not receive a command within this time period Click Save to apply and store the modified parameters Wait for the device to reset After modifying the network settings you will need to use the updated IP address...

Page 8: ...atchdog event 0 Watchdog disabled 1 Watchdog enabled Timeout ref Watchdog timer register set the value in seconds of the Watchdog timer Watchdog Event ref System Flags register this flag signals that the Watchdog condition has occurred 0 Normal condition 1 Alarm condition Power up Event ref System Flags register this flag is forced to 1 at each power on and indicates that the device has been switc...

Page 9: ...Upgrade opens a dialog to enter credentials select a file from the local PC and proceed with the update Firmware Version shows the firmware version loaded on the device WebPage Version shows the version of the web based user interface loaded on the device Do not disconnect power from the device during the upgrade process ...

Page 10: ...1st Edition Username and Password Set the user name and password Username set the user name to access the device Default admin Password set the password to access the device Default password Click Save to apply and store the modified parameters ...

Page 11: ...cted to the input A channel can be disabled by selecting Disabled as its input type Value ref Analog Input registers shows the current value of each analog input Break ref Break register indicates the connectivity status of the sensor If a sensor is disconnected a wire is broken or the sensor is over temperature a red indicator is shown under the break column at that channel Offset sets an offset ...

Page 12: ...er Open a browser and type 192 168 1 174 or the DHCP assigned address in the address field Browse through the user interface to view configuration settings and data or change configuration settings When all changes are complete and saved disconnect power from the device Remove the connection shorting the INIT and VS terminals Apply power to the device and access it from a browser using the configu...

Reviews: