background image

Coopra

 Advanced Heating Technologies b.v.  

Installation and user manual EN_FMT 

  24 

 

CHAPTER 6.  BURNER STATES and MONITORING 
 
6.1.  BURNER STATES 

 

Pump 

  

Standby 

Pre rinse 

Ignition 

In operation 

Post rinse 

afterrun 

Standby 

  

  

  

  

  

  

  

  

  

  

heat demand 

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

fan 

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

gas valve 

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

glow igniter 

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

ionisation 

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

pump 

  

  

  

  

  

  

  

  

  

 

 

t=0sec 

t=3sec 

t=7sec 

  

t<12sec 

  

  

  

 

6.1. Standby 

 

Fan off - Gas valve off - Igniter off - Ionisation off 

 
During the standby, a check is made to see if there is burner 
demand. If so the boiler will go over to pre rise. 
 
If the glow igniter counter is too high (the boiler made too many 
starts repeatidly) the regulation blocks the burner demand. 
 
Once per hour, if there is no heat demand, the difference 
between flow and return temperatures must be less than ± 5°C. 
If this is not the case, the pump will be switched on and a check 
will be made for a maximum of 10 minutes to see whether the 
temperature difference goes to within ± 5°C. 
 
The display shows flashing ‘8’. 
If a false flame signal is detected during standby for more than 
5 seconds, the regulation runs into lock-out with flashing 
indication ‘8’: 
 
 

6.2. Pre rinse 

 

Fan on - Gas valve off - Igniter on - Ionisation off 

 
The difference between flow and return temperatures must be 
less than 20°C before each burner start.  
 
Pump: 
At each new heat demand first the pump is switched off for 3 
seconds and the water pressure (static pressure) is measured 
and stored in the software.  
Then second the pump is switched to high speed and the water 
pressure (active pump pressure) is measured and stored in the 
software. 
 
If the difference between the active pump pressure and the 
static pressure is between 0.05 and 0.54 bar a correct water 
flow throuhg the heat exchanger is present and the ignition time 
starts. 
 

If the difference is less than 0.05 bar or more than 0.54 bar the 
regulation locks. The display shows ‘P’. The regulation runs into 
the “pump test program”.  
 
Fan: 
The fan is switched on at the desired purging speed.  
After a few seconds, the fan goes from purging speed to the 
faster ignition speed. 
 
Glow igniter: 
The glow igniter is switched on at the same time as the fan. 
 
The display shows flashing ‘5’. 
When the measured fan speed deviates from the desired speed 
the regulation blocks. 
After 60 seconds the regulation runs into lock-out, with flashing 
indication ‘5’. 
 
 

6.3. Ignition 

 

Fan on - Gas valve on - Igniter on/off - Ionisation off/on 

 
The fan is running at the ignition speed. The gas valve is 
activated. The glow igniter ignites the gas / air mixture from the 
burner. The glow igniter will be switched off as soon as an 
ionisation signal is measured.  
 
If there is no ionisation at the end of the safety time, a new 
attempt at ignition will be made if this was not the last permitted 
(third) attempt at starting.  
 
 

6.4. In operation 

 

Fan on - Gas valve on - Igniter off - Ionisation on 

 
Temperature test: 
To ensure the water flow through the heat exchanger a 
temperature test is activated.  
The difference between flow and return temperatures must be 
raised by 3°C within 20 seconds after each burner start.  
 

Summary of Contents for SC40

Page 1: ......

Page 2: ......

Page 3: ......

Page 4: ...o high 28 8 11 3 Gas control will not open coils defective 28 8 11 4 Gas Air mixture is not correctly adjusted 28 8 11 5 Check glow igniter 28 8 11 6 Check ionisation current 28 8 11 7 inspection cleaning replacement of the ionisation probe 29 User manual 30 General 30 Cleaning the unit 30 Holidays 30 Brrrr the central heating is not working 30 Electricity and gas 30 Water and air 30 Other causes ...

Page 5: ......

Page 6: ......

Page 7: ......

Page 8: ......

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ... the desired final temperature of the HWS cylinder There is a burner demand when the flow temperature is lower than 85 C and the return temperature is lower than the desired HWS cylinder temperature With HWS cylinder heat demand the pump state is high 5 2 2 2 HWS cylinder with external sensor with modulating space unit The modulating thermostat will generate a desired HWS temperature value The uni...

Page 24: ...ump is switched to high speed and the water pressure active pump pressure is measured and stored in the software If the difference between the active pump pressure and the static pressure is between 0 05 and 0 54 bar a correct water flow throuhg the heat exchanger is present and the ignition time starts If the difference is less than 0 05 bar or more than 0 54 bar the regulation locks The display ...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ......

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ......

Page 33: ......

Page 34: ......

Reviews: