14
3.1.4
F
LOW
T
EMPERATURE OF
65
C
Frame
1
2
3
Model
60
70
80
90
100
U.M.
Power supply
400 - 3 - 50
400 - 3 - 50
400 - 3 - 50
400 - 3 - 50
400 - 3 - 50
V-ph-Hz
IP
Heating A7W65
(Source: Air in 7°C d.b. 6°C w.b. / Plant: Water in 55°C out 65°C)
Heating capacity
60.5
71.2
79.5
89.8
105
kW
Power input
23.8
27.9
31.3
35.3
41.3
kW
COP
2.54
2.55
2.54
2.54
2.54
-
Water flow rate system side
5293
6229
6955
7856
9160
l/h
Pressure drops system side
7
8
8
7
7
kPa
Heating A2W65
(Source: Air in 2°C d.b. 1°C w.b. / Plant: Water in 55°C out 65°C)
Heating capacity
51.8
61.0
68.2
77.0
89.7
kW
Power input
23.8
28.0
31.4
35.3
41.3
kW
COP
2.18
2.18
2.17
2.18
2.17
-
Water flow rate system side
4532
5337
5967
6736
7847
l/h
Pressure drops system side
5
6
6
5
5
kPa
Heating A-4W65
(Source: Air in -4°C d.b. -5°C w.b. / Plant: Water in 55°C out 65°C)
Heating capacity
47.8
56.4
63.0
71.1
82.8
kW
Power Input
23.9
28.1
31.4
35.4
41.4
kW
COP
2.00
2.01
2.01
2.01
2.00
-
Water flow rate system side
4182
4934
5512
6220
7244
l/h
Pressure drop system side
5
5
5
5
5
kPa
Heating A-7W65
(Source: Air in -7°C d.b. -8°C w.b. / Plant: Water in 55°C out 65°C)
Heating capacity
45.3
53.3
59.6
67.3
78.4
kW
Power input
23.9
28.1
31.5
35.4
41.4
kW
COP
1.90
1.90
1.89
1.90
1.89
-
Water flow rate system side
3963
4663
5214
5888
6859
l/h
Pressure drops system side
4
4
4
4
4
kPa
All data declared to
EN 14511
– the above values are referred to units without options or accessories.
Summary of Contents for S-ASX 100
Page 2: ...2 ...
Page 23: ...23 10 CORRECTIVE FACTORS 10 1 Heating Performances ...