Power Cord Summary
2-6
Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide
(R624)
Power Cord Summary
describes where you can find more information about PDU, UPS, and Legacy
E124 expansion storage-system cabinet power cords.
C A U T I O N
!
Place all power cords out of the way of foot traffic.
M I S E E N G A R D E
!
Éloigner tous les cordons d’alimentation du passage.
Main Cabinet Ground Cables
provides information about the main cabinet ground cable.
Table 2-4. Power Cords
Component
Power Cord
UPS (model qualified by
Stratus)
220 VAC input - Customer supplied (hardwired to UPS AC input terminals)
“AC Power Connections to Qualified UPS Models”
PDU
See
“AAP87600V PDU Specifications” on page A-6
Legacy E124
storage-system cabinet
AC source to power strips in the cabinet - See the
Stratus ftServer
Systems: Peripherals Site Planning Guide
(R582)
Table 2-5. Main Cabinet Ground Cable
Component
Cable Description
Stratus PN
Length
Cabinet ground
leakage cable
10AWG ground leakage cable with
1/4 in. (6.35 mm) and M8 ring lugs
AW002000