Circuit Wiring Diagrams
B-6
Stratus ftServer 2600, 4500, and 6300 Systems: Site Planning Guide (R638)
shows a split-phase 120/240V AC circuit connection. Note that this
application requires a double-pole circuit breaker.
Figure B-6. Split-Phase 120/240 Volts AC Circuit Connection
Circuit A or B
X
Y
G (PE)
To power input A or B
Wall
Power Cord
L1
L2
N
G (PE)
240V
120V
0V
120V
Single system: 20A maximum
PDU: 20A maximum