AAP87600 PDU Specifications
System Specifications
A-9
lists the specifications for the AAP87600 PDUs.
Table A-4. AAP87600 PDU: Specifications
Power
Input power
N/A
Nominal input voltage; frequency
200–240 VAC; 50/60 Hz
Physical Dimensions
Height
1.75 in. (4.45 cm)
Width
19.1 in. (48.51 cm)
Depth
6.75 in. (17.15 cm)
Environmental
Operating temperature during
operation
41
F to 95
F (5
C to 35
C)
For every 800 ft (243.8m) above 2000 ft (609.6m), lower
the maximum operating temperature (95
F (35
C)) by
1.8
F (1
C).
Maximum rate of temperature
change during operation
12
C per hour or 0.2
C per minute
Relative humidity during
operation
10% to 80% (noncondensing)
Storage temperature to 40,000 ft
(12.2 km)
-38
F to 140
F (-40
C to 60
C)
Relative humidity during storage
5% to 95% (noncondensing)