Example of PDU Usage Calculation
5-4
Stratus ftServer 2600, 4500, and 6300 Systems: Site Planning Guide (R638)
Example of PDU Usage Calculation
shows how to use the information from
to calculate the required
rack space and the current when the PDU is connected to a NEMA L6-20R receptacle
in the United States, with a voltage of 208V.
and the explanation that follows show how to use the information from
to determine when you need to buy an additional pair of PDUs or calculate
the size and number of cabinets you need.
Table 5-3. Example: Current and Rack-Space Requirements (208 volts)
Component
Watts ÷
Site
Voltage
x 1.25 =
Current (A)
Rack
Space
ftServer system
700
÷
208
x 1.25 =
4.21
4U
1U LCD monitor unit
54
÷
208
x 1.25 =
0.32
1U
Tape drive (typical)
80
÷
208
x 1.25 =
0.48
2U
ftScalable Storage
system
400
÷
208
x 1.25 =
2.40
2U
Table 5-4. Example: Calculating A-Side PDU and Rack-Space Requirements
1. Component
2. Cumulative
Space Used (U)
3. Cumulative
Number of
A-Side Outlets
4. Cumulative
Current (A)
PDU pair
2
0
0.00
ftServer system
6
1
4.21
1U LCD monitor unit
7
2
4.53
Tape drive (typical)
9
3
5.01
ftScalable Storage system
11
4
7.41
ftServer system
15
5
11.62
PDU pair
2
0
0
ftServer system
6
1
4.21
ftServer system
10
2
8.42
Summary of Contents for ftServer 2600
Page 1: ...Stratus Technologies R638 02 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide...
Page 8: ...Tables viii Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Page 48: ...Planning for Cables 3 4 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Page 70: ...Monitor Requirements 6 6 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Page 98: ...Index Index 4 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...