Circuit Wiring Diagrams
Electrical Circuit and Wiring Information
B-7
shows a three-phase 380V AC, Y-, or
-source circuit connection, which is
a phase-to-neutral source connection. Note that the system’s X input can be connected
to L1, L2, or L3. This application requires a single-pole circuit breaker.
Figure B-7. Three-Phase 380V AC, Y-, or D-Source Circuit Connection, Phase-to-Neutral
Circuit A or B
220V
X
Y
G (PE)
To power input A or B
Wall
Power Cord
L1
L2
L3
N
G (PE)
220V
380V
380V
220V
0V
Single system: 20A maximum
PDU: 20A maximum