Boilers – Set the boiler pump to its highest setting.  Set the Boiler Thermostat and 
also the tank thermostat to maximum.  Fire the boiler on HOT WATER ONLY setting 
and wait until the boiler goes off.  Turn the cylinder thermostat down slowly till it 
clicks off, then turn it down by approximately 2⁰C.  This should mean that the tank 
thermostat controls the system.  This can be checked by running off some of the 
hot water, re-firing the boiler and checking that the tank thermostat is in control. 

 

Ensure the store temperature is set to 75⁰C (70⁰C minimum and 80⁰C maximum) 
on the store temperature gauge. This can be increased but consideration should be 
made for the temperature and pressure rise, caused by “creeping”, where  small 
draw offs are present. 

 

On installs where central heating is run from the tank, ensure that 500mm height 
difference  is  in  place  between  the  highest  point  of  the  radiator  circuit  and  the 
bottom of the Feed & Expansion Tank. 

 

Ensure that all exposed pipework on the tank is insulated to minimalise any heat 
losses. 

 

Ensure the Thermostatic Mixing Valve is adjusted to control the hot water outlet 
temperature between 50 - 55°C (take shower differential into consideration). 

 

Check the boiler pump setting is set as high as possible without emitting excessive 
noise to prevent a boiler temperature differential of greater than 11°C. 

 

If required, chlorinate the hot and cold water system in accordance with BS 6700 
and Water Regulations. Please note that the whole of the domestic hot and cold 
water systems must be adequately flushed after chlorination. Failure to do so will 
cause damage to the exchangers/immersion heaters etc. 

DON’T 

 

Use a combined feed and vent. 

 

Use  tube  smaller  than  28mm  between  boiler  and  tank  if  the  boiler  exceeds  an 
output of 60,000 Btu (17kW). 

 

Place any clothing or other combustible materials against or on the tank.

 

 

 

Summary of Contents for Aquatherm STA140UC

Page 1: ...0 Technical Manual Manual must be completed by Installer and left with Home Owner...

Page 2: ...uatherm Connection Heights 3 Technical Data 3 Handling Storage 4 Mains Water Supply 4 Discharge Overflow Requirements 4 Water Treatment 5 Commissioning 6 Immersion Heaters 8 Troubleshooting 9 Aquather...

Page 3: ...3kW Drain Cold Mains Secondary Water c w Y Strainer Hot Out c w Thermostatic Mixing Valve Boiler Coil Return High Efficiency Secondary Coil Ballvalve Boiler Control Stat 75 C Central Heating Flow Ret...

Page 4: ...50 Central Heating Return 105 105 105 105 Boiler Flow 850 1075 1100 1300 Boiler Return 105 105 105 105 Boiler Coil Flow 555 555 555 555 Boiler Coil Return 105 105 105 105 Control Stat 340 300 300 350...

Page 5: ...ate of 20 Litres minute Careful consideration should be made to ensure the pressure of hot and cold supplies are balanced An incoming pressure of 2 1 Bar is the most optimal for performance If the inc...

Page 6: ...em and along with other parts of the primary circuit will require the application of a protective scale and corrosion inhibitor such as Fernox to ensure adequate protection This should avoid having co...

Page 7: ...re plastic to the thermal store system where required Ensure minimum of 225mm between the top of the tank and ceiling to allow access to service the ball valve if ever required Check that all pipework...

Page 8: ...eight difference is in place between the highest point of the radiator circuit and the bottom of the Feed Expansion Tank Ensure that all exposed pipework on the tank is insulated to minimalise any hea...

Page 9: ...nd setting the Immersion Heaters at 70 C and the high limit at 90 C This can be lowered or increased as required for the installation requirements If in any doubt of how to set the Immersion or what t...

Page 10: ...ate is too high then sufficient heat transfer inside may not be occurring Turn the flow through the tap down or fit a suitable flow restrictor and the temperature will increase 3 If Stage 1 and 2 has...

Page 11: ...oked and require cleaning 3 Carefully check the hot water temperature flow into the mixing valve If it is very hot it may be that the valve needs to be checked replaced A competent installer should ch...

Page 12: ...m Spares List Part Number Description SUTMIX1 22mm Thermostatic Mixing Valve SUTVESS1 2 Litre Expansion Vessel SUTSTAT1 Cylinder Thermostat SUTSTRAINER1 22mm Y Strainer SUTBALL1 15mm Ballvalve SUTFLOA...

Page 13: ...monstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference Failure to install and commission this equipment to the manufacturer s ins...

Page 14: ...have been fitted in compliance with Part L of the Building Regulations Yes Type of control system if applicable Y Plan S Plan Other What is the hot water thermostat set temperature C If fitted what is...

Page 15: ...e Building Regulations Yes The system has been installed and commissioned in accordance with the manufacturer s instructions Yes The system controls have been demonstrated and understood by the custom...

Page 16: ...0...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...0 Advanced Water Company Unit D5 Enterprise Way Vale Park Evesham Worcestershire WR11 1GS Tel 01386 760066 Fax 01386 760077 Email sales advancedwater co uk...

Reviews: