Stoveman Crown20R Installation And Operating Manual Download Page 2

 

2.

 

Installation instructions 

 

2.1. Before installation 
We  recommend  performing  the  first  heating  outside  without  heater  stones  before  installing  the  heater,  because  the 
final curing of the external heat-resistant paint of sauna heaters is completed only after heating and the curing process 
may  give  off  an  unpleasant  burning  smell.  Before  that  avoid  scratching  the  metal  parts  of  the  heater.  If  necessary, 
connect a smoke pipe to the flue outlet of the heater to get draft. 
Before installation, make sure that all requirements of safety distances are met. There should be no electrical devices, wires 
or  combustible  materials  around  the  heater  in  the  distances  as  provided  by  the  requirements.  During  installation,  also 
chimney pipe safety requirements must be followed.  
• Installation of the sauna heater must comply with all respective applicable national and EU regulations and standards.  
The heater is also suitable for use in case when several fire chambers have a joint flue pipe, provided that all requirements 
necessary for the operation of the heater are met. The chimney with joint flue pipe must be designed and built in compliance 
with  technical  requirements  of  all  heating  appliances  connected  to  the  joint  flue  and  taking  into  account  their  possible 
simultaneous operation. 
•  Please  ask  for  further  information  on  the  fire  safety  rules  from  local  fire  safety  officials  and  representatives  of  relevant 
supervising authorities. 
• The heater must be installed in such a way that ensures an access to the heater flue pipe and chimney flue for cleaning. 

For installation of the heat exchanger you have to remove the removeable 
rib from the side of the sauna stove. 

 
2.2. Sauna room ventilation 
Sauna room ventilation can be designed and built as a natural or mechanically forced ventilation. 
Natural ventilation can be designed in two ways: 

1)

 

Fresh air inlet is located near the heater close to the floor and its outflow as far as possible from the heater, near the 
ceiling. 

2)

 

Fresh air inlet is located above the heater approximately 500 mm above the upper surface of the stones, and the outlets 
are located as far away from the heater as possible so that the core outlet is placed 50-100 mm higher from the floor and 
the opening required for adjusting comes from the same channel drawn out under the ceiling.  

The grilles installed on the inlet(s) should not impede the necessary amount of air flow.  
Mechanical (forced) ventilation fans may cause problems. 
Forced ventilation systems may only be designed and built by qualified specialists. 
 
2.3. Protecting the floor 
(See Fig. 2) 
N.B. Stoveman heater must be installed onto a floor made of non-flammable material or on a special protective base. 
A. Concrete floor without tiles.  
If  the  concrete  layer  is  at  least  60  mm  thick,  the  heater  can  be  installed  directly  on  the  concrete,  without  applying  any 
additional special precautions. Make sure that there are no electrical cables or water pipes in the concrete beneath the heater.  
B. Tile floor and floor made of combustible material.  
Tile adhesives and mortars, as well as waterproofing materials used under tiles do not tolerate heat radiation coming from the 
heater.  Protect  the  floor  with  a  plate  made  of  stone  or  insulated  metal.  If  the  floor  in  front  of  the  heater  is  made  of 
combustible material, a floor protection of non-combustible material must be installed. 
 
The  floor  under  the  heater  must  be  able  to  withstand  the 
pressure  generated  by  the  legs  of  the  heater  with  stones  and 
chimney.  If  the  existing  floor  cannot  withstand  the  weight  of 
the  heater,  additional  measures  must  be  applied  -  for  example, 
using a load distributing plate. 

 

 

 

2.4. Safety distances to flammable materials 
 (See Fig. 3) 
Safety distances apply for a heater filled with heater stones. 
 
-  Ceiling.  The  minimum  safe  distance  from  the  surface  of 
heater stones to the ceiling is 1200 mm. 
 
- Walls, benches, doors, partitions, and sauna stand made of 
flammable materials. 
The minimum safe distances to flammable materials are:  

 

sides 500 mm; 

 

back  500mm; 

 

front (from the fire chamber door) 1000 mm. 

- Stone walls (KS). Between the side walls and the heater we recommend 
 leaving at least 50 mm wide air gap, provided that air can circulate to the 
 front and one side of the heater. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 2. Floor protection 