Third control level, (A-parameter):
Selection and adjustment
Access to the third control level is granted when selecting the last P-parameter on the second
control level. Continue to press the UP key for approximately 10 seconds until “PA” appears.
Continue to press the UP key and additionally press the DOWN key for about 4 seconds and the
first A-parameter of the third control level is indicated.
With the keys UP and DOWN you can scroll the list in both directions. Pressing the SET TIME key
will give you the value of the respective parameter. By pressing the UP or DOWN key at the same
time the value can be adjusted.
Return to the initial position takes place automatically, if no key is pressed for 60 seconds, or by
simultaneously pressing the UP and DOWN key for approx. 4 seconds.
Para-
meter
Function description
Adjustment range
Standard
setting
Custom
setting
A1
Switch mode contact K1
0: heating contact
1: cooling contact
0
A3
Function of contact K1 at
sensor error
0: relay off
1: relay on
0
A8
Display mode
(all parameter indications
are presented in 0,1°K)
0: integrals
1: decimals in 0.5°C
2: decimals in 0.1°C
1
A19
Parameter lock
0: no lock
1: A-parameter locked
2: A- and P-parameter locked
0
A30
Function alarm exit
0: Boundary alarm, relative
1: Boundary alarm, absolute
2: Range alarm, relative
3: Range alarm, absolute
4: Boundary alarm, relative,
alarm contact inverted
0
A31
Special function at
boundary or range alarm
0: no special function
1: flashing display
2: buzzer
3: flashing display and buzzer
4: like 3, buzzer can be
cancelled
5: like 4, buzzer restarts
after 10 min.
6: like 4, buzzer restarts
after 30 min
0
A32
Setpoint display
0: display shows actual value
1: display shows setpoint S1
0
A33
Type of setpoint S1‘
0: not activated
1: relative to setpoint S1
2: absolute (freely adjustable)
0
A40
Hysteresis mode contact
K1
0: symmetrically
1: one-sided
1
A50
Minimum action time
contact K1 ”On”
0…999 sec.
0 sec.
A51
Minimum action time
contact K1 ”Off”
0…999 sec.
0 sec.
A54
Delay after “Power-on”
0…999 sec.
0 sec.