Selection/activation of PID programs "Pr.1...Pr.3" 

To select or activate the PID programs, button "UP" must be pressed for approx. 2 seconds on 
reference value level. The controller will then switch to program selection level, where you can set 
a pointer to programs "Pr.1...Pr.3" using buttons "UP" and "DOWN". To select the program on the 
display, press "SET" button for approx. 2 seconds. The display will be flashing indicating that the 
program was selected successfully. 
To return to the reference value level from "PR.1" position, simply press the "DOWN" button for 
approx. 2 seconds or perform an Auto Reset, for which a shorter waiting time of approx. 10 
seconds is implemented. 
If the actual value reaches the limit defined via "P7", the controller will activate the selected 
program automatically and maintain it until the actual value drops below the limit again. Above the 
limit, programs "Pr.1...Pr.3" are not only selected in the way described above, but also activated 
immediately.  
 

Activation of PID program "Pr.4" 

Above the limit value defined via "P7" you can use the quick-heating button ("turbo button") to 
switch from the pre-selected/activated program "Pr.1...Pr.3" to "Pr.4" and back. Pre-selection of 
"Pr.4" is not possible during the first heating phase. If "Pr.4" is active, parameter "A1" determines if 
thermostat behavior or PID characteristic based on parameters "P20-P23" is active. Programs 
"Pr.1...Pr.3" always have PID characteristic. The appliance is designed such that maximum heating 
power is always guaranteed for program "PR.4", irrespective of parameterization. 
 

Automatic return to slow heating 

If, with program "Pr.1...Pr.4" activated, the actual temperature drops below the fixed limit of 50 °C, 
the controller returns to slow heating mode automatically. In this case, as well as after "Mains 
supply On", it is only possible to switch between "Pr.1" and slow heating. This switching option is 
given both below and, after brief heating, above 50 °C. Activation of "Pr.2...Pr.4" is deleted, pre-
selection of "Pr.2" or "Pr.3" is maintained. 
 

Function of indicator lamps 

The upper lamp "H" indicates the switching state of the output contact. The lamp in the middle 
"Slow heating" indicates that the slow heating phase is active. The bottom lamp "Quick heating" 
lights up only if program "Pr.4" is active. Lamps "Slow heating" and "Quick heating" are always off 
if one to the programs "Pr.1...Pr.3" are active. 
 

Displaying the active program 

Press buttons "ON/OFF" and "Turbo" at the same time to display the actually active program for 
approx. 4 seconds. Since the individual functions assigned to the two buttons will be activated only 
after a delay of approx. 2 seconds, unintentional activation of these functions is not possible if you 
press the two buttons simultaneously, as the selected program will be displayed right away. This 
display does not affect the control behavior or the controller settings. In slow heating mode, the 
display will not respond if you press the buttons. 
 

Hot fat operating hours counter and alarms 

In internal counter registers the operating time with hot fat. The counter will be active only if the 
actual value is above the temperature set in parameter "P25". Once the time set in parameter 
"P26" has elapsed, a fat warning will be triggered. The regular display and the warning "OIL" will 
be displayed alternately. In this state, the controller remains operational, parameters can be set, 
too. Once the time set in parameter "P27" has elapsed, control will be blocked. Now, all functions 
of the controller are disabled and control is deactivated. Only switching to "standby" mode is 
possible now. To indicate this state, only the "OIL" message on the display will be flashing. 
The fat warning message and control blocking must be activated via parameters "A2" and "A3". If 
activated later, it must be noted that the hot fat operating time is registered regardless of  the 
activation and the alarm functions (warning/blocking) can be triggered immediately or a short time 
after activation. The current fat operating time can be checked in parameter "P28". This value 

Summary of Contents for ST96 Series

Page 1: ... and is foreseen for use with deep fryers The unit has a 3 digit display and is supplied with 230V AC The controller has an input for Pt100 temperature sensor and one relay exit The control setpoints and parameters determining the process are adjusted with a 5 field plastic foil keyboard Sensor Pt100 Range 99 850 C Front size 96mm x 96mm Panel cut out 90 5mm x 90 5mm Connector plug and socket ...

Page 2: ......

Page 3: ...ss the turbo button Press the button again to return to slow heating mode This button must also be pressed for approx 2 seconds to prevent unintentional switching Heating with hot fat When the fat is already hot when mains supply is turned on and the controller is turned on by pressing the ON OFF button the control behavior which will be activated depends on the fat temperature The clock end defin...

Page 4: ...ng above 50 C Activation of Pr 2 Pr 4 is deleted pre selection of Pr 2 or Pr 3 is maintained Function of indicator lamps The upper lamp H indicates the switching state of the output contact The lamp in the middle Slow heating indicates that the slow heating phase is active The bottom lamp Quick heating lights up only if program Pr 4 is active Lamps Slow heating and Quick heating are always off if ...

Page 5: ... is blocked the controller will return to reference value level in any case and Pr 2 Pr 4 will be deactivated after the reset slow heating will be active below the limit value defined in P7 above this temperature Pr 1 will be active Switch off delay for gas heating design For use with heating types which start after a delay due to their design a switch off delay can be defined for the output relay...

Page 6: ...er P7 you can stop the slow heating phase before the setpoint is reached If this is not desired set P7 0 0 K Figure 1 Heating phase after slight cooling refer to Figure 2 After minor cooling to temperatures above 50 C e g loading of small quantities of cold fat the normal heating function of the controller is maintained The new heating phase will not be slowed down the heating relay will not be cl...

Page 7: ...ion By pressing the quick heating button you can switch over to the normal heating function Now the fat will be heated more quickly The heating relay will no longer clock based on the times set in parameters P1 and P2 but based on the PID function set within program Pr 1 The clock end defined via parameter P7 does not have any influence after the manual intervention To undo the change over press t...

Page 8: ...tion mode with slow heating phase when the controller is switched on and started or restarted later or in the case of cool down to temperatures below 50 C The switch back threshold is can be set via parameter P79 First control level Setting the main reference values and reference value setback The main reference value can be viewed by pressing the SET button Press UP or DOWN key additionally to ch...

Page 9: ... 99 0 K 0 8 K P4 Lower setpoint limit 60 0 999 C 60 0 C P5 Upper setpoint limit 60 0 999 C 190 C P6 Actual value correction 10 10 0 K 0 0 K P7 Clock end below threshold 99 0 0 K 30 K P8 Proportional term Pr 1 0 1 99 0 K 5 0 K P9 I term Pr 1 0 15 12 P10 D term Pr 1 0 15 15 P11 Cycle time Pr 1 8 100 sec 12 sec P12 Proportional term Pr 2 0 1 99 0 K 5 0 K P13 I term Pr 2 0 15 12 P14 D term Pr 2 0 15 1...

Page 10: ...ctive additively in the whole measuring range P7 Clock end below reference value With this parameter you can terminate the clocked heating phase while the temperature is still below the reference value If clocked heating is to be active until the reference value is reached set P7 0 0 K P8 Proportional term Pr 1 Setting of proportional term for PID program Pr 1 In the proportional term power supply...

Page 11: ...erating times set in parameters P26 and P27 are exceeded a warning message will be displayed or control will be blocked P26 Fat operating time until warning message Here you can set the time after which a warning will prompt the user to replace the used frying fat P27 Fat operating time until controller blocked Here you can set the time after which control will be blocked and the user will have to...

Page 12: ...1 active 0 Description of parameters The following values affect the properties of the appliance and any changes should be considered carefully for this reason A1 Control characteristic in turbo program Pr 4 Here you can define the control characteristic to be used while program Pr 4 is active You can choose between thermostat behavior and PID characteristic based on parameter group P20 P23 The co...

Page 13: ... digit LED displays 13 und 10 mm height colour red 3 LEDs diameter 3mm for status display Power supply 230V 50 60Hz Connectors plug and socket Ambient conditions Storage temperature 20 70 C Operating temperature 0 55 C Relative humidity max 75 without dew Enclosure Front IP50 Installation data Front size 96 x 96 mm Panel cut out 90 5 x 90 5 mm Installation depth ca 105 mm with connector Mounting b...

Reviews: