Boundary alarm function (see fig. 5): 
The alarm contact is closed if the process 
temperature is above the upper or below the lower 
boundary value.  

 
 
 
 
 

 
 
 
 

Fig. 5: Boundary alarm, rel. boundaries

Range alarm function (see fig. 6): 
Opposite switching behaviour to the boundary 
value alarm. The alarm contact is closed if the 
actual value remains between the boundary 
values

 
 
 
 
 
 
 
 

Fig 6: Range alarm, abs. boundaries 

 

P32: Hysteresis alarm circuit 

Hysteresis is set symmetrical at the adjusted limit value, i.e. half of the hysteresis’ value is effective below 
and half of the value above the switching point 
 

 

Third control level, (A parameters): 
 
Setting of control parameters 

Access to the third control level is granted when selecting the last P-parameter on the second control level. 
Continue to press the UP key for approximately 10 seconds until “PA” appears. Continue to press the UP 
key and additionally press the DOWN key for about 4 seconds and the first A-parameter of the third control 
level is indicated. 
With the keys UP and DOWN you can scroll the list in both directions. Pressing the SET key will give you the 
value of the respective parameter. By pressing the UP or DOWN key at the same time the value can be 
adjusted. 
Return to the initial position takes place automatically, if no key is pressed for 60 seconds, or by 
simultaneously pressing the UP and DOWN key for approx. 4 seconds. 

 

Para-
meter 

Function description 

Adjustment range 

Standard 
setting 

Custom 
setting 

A1 

Switch mode contact K1 

0: heating contact 
1: cooling contact 

 

A2 

Switch mode contact K2 

0: heating contact 
1: cooling contact 

 

 

A3 

Function of contact K1 at 
sensor error 

0: relay off 
1: relay on 

 

A4 

Function of contact K2 at 
sensor error 

0: relay off 
1: relay on 

 

A5 

Selection setpoint 2 or DeltaW  0: operation with setpoint 2 

1: operation with DeltaW 

 

 

A8 

Display mode 
(all parameter indications are 
presented in 0.1°K) 

0: integrals, without leading zero 
1: with decimals without leading zero 
2: integrals, with leading zero 
3: with decimals and leading zero 

 

 

A9 

Weighing factor 

0.50 ... 2.50 

1.00 

 

A10 

Indication value for lower 
value linear analogue input 

-99...999 

0,0 

 

A11 

Indication value for upper 
value linear analogue input 

-99...999 

100 

 

A19 

Parameter lock 

0: no lock 
1: A-parameter locked 
2: A- and P-parameter locked 

 

Summary of Contents for ST72-31.03

Page 1: ...oint controller with alarm contact three point controller with alarm contact two stage controller with alarm contact three stage controller The setpoint and all parameters of the controller are set on a three field plastic foil keyboard Range dependent on type of sensor Front size 72mm x 72mm Panel cut out 66 5mm x 66 5mm Connector plug and socket Power supply 230V ...

Page 2: ......

Page 3: ...f the keys is pressed the display indicates the actual value of the temperature Pressing the SET key the setpoint shows on the display If the setpoint is to be changed the SET key is to be kept pressed while adjusting the setpoint with the keys UP and DOWN Please note that the setpoint can only be changed within the set setpoint limits The setpoint S1 if available can be adjusted in the same way I...

Page 4: ...tial position takes place automatically if no key is pressed for 60 seconds Para meter Function description Adjustment range Standard setting Custom setting P1 Setpoint 2 or DeltaW P4 P5 99 999 K 10 0 C P2 Hysteresis contact K1 0 1 99 0 K 1 0 K P3 Hysteresis contact K2 0 1 99 0 K 1 0 K P4 Control range limitation minimum setpoint 99 C P5 99 C P5 Control range limitation maximum setpoint P4 999 C 9...

Page 5: ...ange limitation maximum setpoint The adjustment range of the setpoint can be limited in both directions This is to prevent the end user of a unit from setting inadmissible or dangerous setpoints P6 Actual value correction This parameter allows the correction of actual value deviations caused for example by sensor tolerances or extremely long sensor lines The regulation measure value is increased o...

Page 6: ...st in both directions Pressing the SET key will give you the value of the respective parameter By pressing the UP or DOWN key at the same time the value can be adjusted Return to the initial position takes place automatically if no key is pressed for 60 seconds or by simultaneously pressing the UP and DOWN key for approx 4 seconds Para meter Function description Adjustment range Standard setting C...

Page 7: ...y adjustable 0 A34 Indication of setpoint change over 0 not active 1 flashing right point 0 A40 Hysteresis mode contact K1 0 symmetrically 1 one sided 0 A41 Hysteresis mode contact K2 0 symmetrically 1 one sided 0 A50 Minimum action time contact K1 On 0 400 sec 0 sec A51 Minimum action time contact K1 Off 0 400 sec 0 sec A52 Minimum action time contact K2 On 0 400 sec 0 sec A53 Minimum action time...

Page 8: ...nalogue input Only relevant if the controller is programmed for a voltage input 0 10V linear or a current input 4 20mA linear These parameters allow scaling of the linear analogue input The value to be indicated for the lower and upper entrance value then defines the range the controller will indicate For input range 4 20mA the display will show sensor error if the input signal drops below 4mA A19...

Page 9: ...acts K1 and K2 This parameter makes a mutual switching on delay of relays possible depending on whichever contact is switched first A56 Alarm Delay after Power on or setpoint changeover This parameter allows a delay of the alarm after switching on the mains voltage or after a setpoint changeover with switching input E1 A80 Temperature scale Indication can be switched between Fahrenheit and Celsius...

Page 10: ...t 4A 250V cosϕ 1 K2 Relay change over contact 4A 250V cosϕ 1 K3 Relay normally open contact 4A 250V cosϕ 1 Display One 3 digit LED displays height 13 mm for temperature display colour red Three LEDs for status display of the outputs K1 K2 and K3 Power supply 230V 50 60Hz Connectors plug and socket Ambient conditions Storage temperature 20 C 70 C Operating temperature 0 55 C Relative humidity max 7...

Page 11: ...r Ni Connection clamp 12 and 13 Dip switch 1 and 2 in position ON ON 6 Connection KTY81 121 PTC Connection clamp 11 and 13 Dip switch 1 5 and 6 in position ON ON 6 Connection Current input 4 20 mA Connection clamp 12 and 13 if FF20 DF17 sensor clamp 14 und 12 Dip switch 1 2 3 and 5 in position ON ON 6 Connection Voltage input 2 10 V Connection clamp 12 and 13 Dip switch 1 3 and 6 in position ON ON...

Reviews: