Second control level (P parameters):
Setting of control parameters
Simultaneously pressing the UP and DOWN key for at least 4 seconds opens a parameter list
containing control parameters.
With the UP and DOWN keys the list can be scrolled in both directions.
Pressing the SET key will give you the value of the respective parameter. Pressing also the UP or
DOWN key at the same time the value can be adjusted.
Return to the initial position takes place automatically, if no key is pressed for 60 seconds.
Para-
meter
Function description
Adjustment range
Standard
setting
Custom
setting
P1
Setpoint 2 or
DeltaW
P4...P5
-99...+999 K
0,0°C
+10K
P2
Hysteresis contact K1
0.1... 99.9 K
1.0 K
P3
Hysteresis contact K2
0.1... 99.9 K
1.0 K
P4*
Control range limitation –
minimum setpoint
-99°C...P5
-99°C
P5*
Control range limitation –
maximum setpoint
P4...999°C
999°C
P6
Actual value correction
-10.0...+10.0 K
0.0 K
P11**
Relative or
absolute employment point of
the ramp phase
-99...99K
-99...999°C
10.0K
10.0°C
P12**
Ramp gradient
0.1...100K/min.
10.0K/min.
P19
Key-lock
0: no key-lock
1: key-lock
0
P30
Lower alarm value
-99...999°C/K
-10.0 K
P31
Upper alarm value
-99...999°C/K
+10.0 K
P32
Hysteresis alarm circuit,
symmetrical
0.1...99.9 K
1.0 K
*
standard setting depends on sensor type
** parameter only available with activated ramp function