Third control level, (A parameters): 
 
Setting of control parameters 

Access to the third control level is granted when selecting the last P-parameter on the second 
control level. Continue to press the UP key for approximately 10 seconds until “PA” appears. 
Continue to press the UP key and additionally press the DOWN key for about 4 seconds and the 
first A-parameter of the third control level is indicated. 
With the keys UP and DOWN you can scroll the list in both directions. Pressing the SET key will 
give you the value of the respective parameter. By pressing the UP or DOWN key at the same time 
the value can be adjusted. 
Return to the initial position takes place automatically, if no key is pressed for 60 seconds, or by 
simultaneously pressing the UP and DOWN key for approx. 4 seconds. 
 
 
 

Para-
meter 

Function description 

Adjustment range 

Standard 
setting 

Custom 
setting 

A1 

Switch mode contact K1 

0: heating contact 
1: cooling contact 
2: function alarm K1 

 

A3 

Function of contact K1 at 
sensor error 

0: relay off 
1: relay on 

 

A8 

Display mode 
(all parameter indications are 
presented in 0.1°K) 

0: integrals 
1: decimals in 0.5°C 
2: decimals in 0.1°C 

 

 

 

A19 

Parameter lock 

0: no lock 
1: A-parameter locked 
2: A- and P-parameter locked 

 

A30 

Function alarm exit 

0: Boundary alarm, relative 
1: Boundary alarm, absolute 
2: Range alarm, relative 
3: Range alarm, absolute 
4: Boundary alarm, relative, 
   inverted alarm contact 
5: Boundary alarm, absolute, 
   inverted alarm contact 
6: Range alarm, relative, 
   inverted alarm contact 
7: Range alarm, absolute, 
   inverted alarm contact 

 

A31 

Special function at boundary or 
range alarm 

0: no special function 
1: flashing display 
2: buzzer 
3: flashing display and buzzer 
4: like 3, buzzer can be cancelled 
5: like 4, buzzer restarts after 10 min. 
6: like 4, buzzer restarts after 30 min 


 

 

A32 

Setpoint display 

0: display shows actual value 
1: display shows setpoint S1 (S1‘) 

 

A33 

Type of setpoint S1‘ 
 

0: not activated 
1: relative to setpoint S1 
2: absolute (freely adjustable) 

 

A40 

Hysteresis mode contact K1 

0: symmetrically 
1: one-sided 

 

 

Summary of Contents for 900321.003

Page 1: ...binet It was specifically developed for direct switching at high per formances Given the high maximum electric load of 16A ohm and 6A inductive it can operate without cut out relay in many cases The c...

Page 2: ......

Page 3: ...essed the display indicates the actual value of the temperature Pressing the SET key the setpoint shows on the display If the setpoint is to be changed the SET key is to be kept pressed while adjustin...

Page 4: ...o key is pressed for 60 seconds Para meter Function description Adjustment range Standard setting Custom setting P0 Actual measuring value P2 Hysteresis contact K1 0 1 99 9 K 1 0 K P4 Control range li...

Page 5: ...ances or extremely long sensor lines The regulation measure value is increased or decreased by the here adjusted value P19 Key lock The key lock allows blocking of the control keys In locked condition...

Page 6: ...mperature value is reached The defrosting time set with d3 nevertheless runs at the same time i e it functions as safety net to terminate the defrosting process in case the defrosting temperature is n...

Page 7: ...t 1 cooling contact 2 function alarm K1 0 A3 Function of contact K1 at sensor error 0 relay off 1 relay on 0 A8 Display mode all parameter indications are presented in 0 1 K 0 integrals 1 decimals in...

Page 8: ...re scale and display when in Standby Mode 0 Fahrenheit AUS 1 Celsius AUS 2 Fahrenheit OFF 3 Celsius OFF 1 A85 Function key A if available 0 no function 1 indicate actual value if A32 1 2 activate setp...

Page 9: ...m is released if the temperature lies beyond them In the case of sensor error the alarm is activated independently of this adjustment see fig 3 4 at parameters P30 31 A31 Special function at boundary...

Page 10: ...ameter can determine by how many measured values an average value is to be formed If a sensor with a very fast reaction to external influences is used an average value ensures a calm signal process A8...

Page 11: ...lock active Change parameter P19 or A19 display flashes Temperature alarm at too high or too low temperature if activated see A31 Buzzer Temperature alarm at too high or too low temperature if activa...

Page 12: ...conductive strips Display One 3 digit LED Display height 13 mm colour red 1 LED diameter 3mm colour red for status display of K1 Power supply 230V 50 60 Hz power consumption max 5 VA Connectors screw...

Reviews: