Order number: 900228.023 

Page 4 

Configure gateway 

 

After you have adjusted the local network settings of your PC, press the "Configure Gateway..." button. 

 

 

The factory settings of the gateway are displayed. Please do 

not change anything, just activate the "verbinden" 

(“connect”) button. The current settings of the IP gateway 

are displayed in the lower dialogue section.  

 

If you receive an error message, please check the network 

settings and cable connections, reconfigure any existing 

firewall to allow ICMP packets and ports 14742 and 14743 to 

pass through or contact your network administrator. 

 

After you have established a successful connection to the IP 

gateway, you can make the settings valid in your local 

network. 

 

For setting the locally valid network defaults, please perform 

the following actions: 

 

 

Enter the static IP address for the IP gateway obtained from 

your network administrator as the "IP address". Proceed in 

the same way with the entries "Subnet mask" and "Default 

gateway". 

 

 

To save the values in the IP gateway, you must enter the password and the password confirmation. In the 

factory setting, the password is "administrator". Then please activate the button "configure". 

 

You can change the password by entering a new password in the fields "Password" and "Password 

confirmation" and then pressing the button "Configure". Please wait at least 10 seconds until the gateway 

has reinitialised. 

 

If you have made a mistake when entering the settings or decide to return to the original values, you can 

reset the gateway to the factory settings by pressing the "RESET" button for at least 3 seconds. 

.

Summary of Contents for 900228.023

Page 1: ...00228 023 As of 11 12 2015 Wiring diagram Product description With the help of the TCP IP RS485 interface coupler an RS485 interface is made available on a computer with an Ethernet connection for communication with ST Bus devices Dimensions approx 140mm x 85mm x 50mm Wall mounted housing ...

Page 2: ...u want to operate several IP gateways please make sure that only one IP gateway to be configured is connected to the local network at any one time If the default IP address of the gateway 192 168 0 101 is not used in your local network you can connect the gateway to the local network using a CAT5 Ethernet cable If the default IP address is already assigned connect the gateway directly to your PC f...

Page 3: ...ke a note of the original values of the properties window You will need these values when you reconnect the PC to your local network If your PC is already in the subnet 192 168 0 xxx the IP address is composed of 192 168 0 in the first three entries you can skip the following points cancel all dialogues and continue directly with the point Configure gateway If the PC is in another subnet the IP ad...

Page 4: ...your local network For setting the locally valid network defaults please perform the following actions Enter the static IP address for the IP gateway obtained from your network administrator as the IP address Proceed in the same way with the entries Subnet mask and Default gateway To save the values in the IP gateway you must enter the password and the password confirmation In the factory setting ...

Page 5: ... conditions Storage temperature 20 C 70 C Working temperature 0 55 C Relative humidity max 75 r h no condensation Power supply 230V 50 60 Hz power consumption 3VA Weight Ca 200g Tightness IP42 Installation data Table top housing also suitable for screwing to a wall Enclosure size L 140mm x W 85mm x H 50mm ...

Reviews: