Partially reset EEPROM to
pressure operation
:
for refrigerant R134A (A37 = 0)
Setpoints 1 and 1’
S1 = 2.0 bar
(or 0.7°C)
S1' absolute = 2.0 bar
S1' relative = 0.0 bar
A59 = 0.0 K
Setpoints 2 to 6
P1 absolute = 3.1 bar
(or 9.6°C)
P1 relative = 1.1 bar
P2 absolute = 4.6 bar
(or 19.3°C)
P2 relative = 2.6 bar
P3 absolute = 6.7 bar
(or 29.9°C)
P3 relative = 4.7 bar
P4 absolute = 9.2 bar
(or 40.1°C)
P4 relative = 7.2 bar
P5 absolute = 12.1 bar
(or 49.8°C)
P5 relative = 10.1 bar
Hysteresis
P11 – P16 = 0.2 bar
(or 1.7 K)
Control range limitations
P17 = 0.0 bar (or -26.4°C at 4.0 mA)
P18 = 30.0 bar (or 87.5°C at 20.0 mA)
Actual value correction
P21 = 0.0 bar
Alarm limit values
P30 absolute = 0.0 bar
P30 relative = -1.0 bar
(2.0-1.0 bar or -10.1°C for -10.0 K)
P31 absolute = 30.0 bar
P31 relative = 1.1 bar
(2.0+1.1 bar or 9.6°C for +10.0 K)
Alarm hysteresis
P32 = 0.2 bar
(or 1.7 K)
for refrigerant R22 (A37 = 1)
Setpoints 1 and 1’
S1 = 4.1 bar
(or 0.5°C)
S2 absolute = 4.1 bar
S2 relative = 0.0 bar
A59 = 0.0 K
Setpoints 2 to 6
P1 absolute = 5.8 bar
(or 10.0°C)
P1 relative = 1.7 bar
P2 absolute = 8.0 bar
(or 19.7°C)
P2 relative = 3.9 bar
P3 absolute = 10.9 bar
(or 30.0°C)
P3 relative = 6.8 bar
P4 absolute = 14.2 bar
(or 39.8°C)
P4 relative = 10.1 bar
P5 absolute = 18.4 bar
(or 50.1°C)
P5 relative = 14.3 bar
Hysteresis
P11 – P16 = 0.2 bar
(or 1.9 K)
Control range limitations
P17 = 0.0 bar (or -41.1°C at 4.0 mA)
P18 = 30.0 bar (or 71.7°C at 20.0 mA)
Actual value correction
P21 = 0.0 bar
Alarm limit values
P30 absolute = 0.0 bar
P30 relative = -1.6 bar
(4.1-1.6 bar or -10.4°C for -10.0 K)
P31 absolute = 30.0 bar
P31 relative = 1.7 bar
(4.1+1.7 bar or 10.0°C for +10.0 K)
Alarm hysteresis
P32 = 0.2 bar
(or 1.9 K)