Instructions for the installer
3.7 REVERSING THE CONNECTIONS
Th
e ARES Tec ErP boiler leaves the factory set up for hydraulic
(flo
w
and return), gas and
fl
ue exhaust connections located on the RIGHT
side of the boiler.
Reversing FLUE GAS
To move the
fl
ue exhaust to LEFT simply switch the two sides of the
casing around.
FOR MODELS 250 - 300 - 350
To move the
fl
ue exhaust from Right (standard posi-
tion) to the rear position, you need to request the
optional
fl
ue kit consisting of the Ti shown in the
figur
e and a closing plate for the hole in the Rh side
of the casing.
FOR MODELS 150 - 200
it is necessary to request the
fl
ue kit comprised of a
closing plate over the hole on the Rt side of the casing. .
Reversing GAS
To move the gas connection,
switch the blin
d fl
ange with
th
e fl
anged stub pipe.
Reversing SYSTEM FLOW AND RETURN
To move the Flow / Return connections to the opposite side,
switch the blin
d fl
ange with
th
e fl
anged stub pipe.
To move the hydraulic
connections (one or both) to
the LEFT side, remove the
pre-sectioned part on the
attachments that you intend to
move to the opposite side and
close the RIGHT side of the
casing with the caps supplied
with the boiler.